JDL26250 SQUARE D, JDL26250 Datasheet
JDL26250
Specifications of JDL26250
Related parts for JDL26250
JDL26250 Summary of contents
Page 1
Contents Description Selection Information • Feature Information • Selection Information, Commercial Circuit Breakers • Selection Information, Industrial Circuit Breakers • Application Data (Single Motor Branch Circuits) QOU Miniature Circuit Breakers • QOU Series 3 Unit Mount Breakers • QOU Accessories ...
Page 2
... X RL 600-2500 X Except 1 Pole Accesories may be provided in automatic moulded case switches, with the exception of QB, QD, QG, QJ. MAG-GARD® circuit breakers accept the same lugs & accessories as equivalent thermal-magnetic circuit breakers. Square D Micrologic® Series B Features Zone Local Circuit Selective Current Breakers ...
Page 3
Catalogue Number Prefix Plug-On Bolt-On Unit Mt. I-Line QO QOB QOU QO-H QOB-H QO-VH QOB-VH QH QHB QOT QO-GFI QOB-GFI QO-AFI QOB-AFI QO-VHGFI QOB-VHGFI QBL QBA QDL QDA QGL QGA QJL QJA Q4L Q4 UL/CSA certified for 1 and 2 ...
Page 4
Moulded Case Circuit Breakers Selection Information Industrial Thermal-Magnetic Circuit Breakers Electronic Trip Circuit Breakers Catalogue No. Cont. Number Prefix of Ampere Poles Rating Unit Mount I-LINE Q4L Q4 2,3 250-400 FAL FA 1 15-100 240V. 240V. 2,3 15-100 FAL FA ...
Page 5
... Heavy service is jogging or plugging duty or cycling load with over 25 starts per hour or 5 starts per minute. Thermal - Magnetic Breaker recommended trip ratings are approximate for average conditions and are based on trip characteristics of Square D Breakers. Selection Tables for Conductors and Thermal-Magnetic Circuit Breakers Minimum Size QMB & ...
Page 6
Moulded Case Circuit Breakers QOU Thermal-Magnetic Trip Unit Mounting QOU260, Din Rail Mounted No. of Description AIR Voltage Amp. Poles Rating Rating Rating One Thermal- 10,000 120/240 10 Magnetic AIR Vac 15 Circuit 15 Breaker ...
Page 7
... OEM Mounting Bases 4 Pole Jumper Bar Assembly Base QOU14100BAFB Cover and Cover Screw QOU14100CAB QOURT Field Installable Ring Tongue Terminal Connector Crimp connectors are not included with Square D connectors QOUEC Field Installable Quick Connector 2-Pole DIN Mounted QOU Circuit QON2L40 DE3-7 ...
Page 8
... Circuit Protection That Meets Your Specific Needs To help you get the right protection for your electrical system, SQUARE D offers a comprehensive selection of thermal-magnetic moulded case circuit breakers. They span the full range of CSA certified and UL listed interrupting ratings, standard, high, extra high and current limiting. In addition, our thermal- magnetic line includes an unmatched choice of constructions, voltage and ampere ratings ...
Page 9
Thermal-magnetic moulded case circuit breakers shown here are permanent trip CSA certified, UL listed, IEC rated. For I-LINE moulded case circuit breakers, see Section DE-5. AC Magnetic One Pole Two Pole Ampere Trip Settings Rating Amperes Catalogue No. Price Catalogue ...
Page 10
... Number Number 750 1500 JDL26150 JGL26150 875 1750 JDL26175 JGL26175 1000 2000 JDL26200 JGL26200 1125 2250 JDL26225 JGL26225 1250 2500 JDL26250 JGL26250 750 1500 JDL36150 JGL36150 875 1750 JDL36175 JGL36175 1000 2000 JDL36200 JGL36200 1125 2250 JDL36225 JGL36225 1250 2500 JDL36250 ...
Page 11
H-frame 150 A 3-pole Thermal-magnetic Frame Only (600 Vac) without terminations D Interrupting G Interrupting Ampere Catalogue Catalogue Rating Price Number Number 15–60 A HDF36000F06 HGF36000F06 70–150 A HDF36000F15 HGF36000F15 J-frame 250 A 3-pole Thermal-magnetic Frame Only (600 Vac) without ...
Page 12
Moulded Case Circuit Breakers Powerpact Q 250 Ampere Frame POWERPACT Q-frame —250 A, Thermal-magnetic (240 Vac Magnetic 10,000 AIR Continuous Trip Settings Current Rating Catalogue @ 40°C Hold Trip Number 2-pole, 240 Vac 70 1000 1800 QBL22070 80 ...
Page 13
KAL/KHL Two & Three Pole 70-250 Ampere CSA Certified Interrupting Rating RMS Symmetrical Amperes Breaker System Voltage AC Cat. No. 240 480 600 125 Prefix KAL 42k 25k 22k 10k KHL 65k 35k 25k 10k KCL 100k 65k Q4L 25k ...
Page 14
Moulded Case Circuit Breakers FIL - KIL - LIL Current-Limiting Circuit Breakers 100, 250, 400 & 600 Ampere Frame CSA Certified Interrupting Rating RMS Symmetrical Amperes Breaker System Voltage AC Cat. No. Prefix 240 480 600 FIL 200k 200k 100k ...
Page 15
... Max. STANDARD moulded case switches provide no overcurrent protection or short circuit protection. They must not be used on systems that have an available fault current greater than the values listed in the table below. AUTOMATIC moulded case switches open instantaneously at a factory preset magnetic trip point, calibrated to protect only the moulded case switch itself, when it is subjected to high fault currents ...
Page 16
... Available only for single mount. The CK breaker can not be replaced in existing 12X of branch circuit height, the Square D PowerPact breaker requires space with a 16X branch nominal height. Contact Schneider Services for installation of PowerPact P breaker and mounting hardware. ...
Page 17
D-frame (600 A 600 Vac) 3P 50/60 Hz Circuit Breaker with Lugs and Electronic Trip Units Electronic Trip Trip Continuous Trip Unit Unit Type Function Current 150 A 250 A LS STR23SP 400 A 600 A 150 A 250 A ...
Page 18
Moulded Case Circuit Breakers Powerpact 800, 1200, 2500 A Frame M-frame Unit Mount P-frame Standard Trip Unit R-frame Circuit Breaker M-, P-frame Circuit Breaker Termination Options (Third character of catalogue number) F=No Lugs L=Lugs both ends M=Lugs ...
Page 19
... By joining a sensitive measuring capability with sophisticated logic, this tech- nology allows you to customize your circuit protection system to meet your application needs. For example, you can establish specific characteristic tripping responses for each circuit breaker by setting individual current-re- sponse levels and introducing intentional time delays for coordination with downstream components ...
Page 20
Moulded Case Circuit Breakers ® MICROLOGIC Series B Trip Systems Features Standard and Full-Function L-frame—600 A, Micrologic Series B Trip System 3P, 600 V Sensor Ampere Size Rating 250 Circuit Breakers with Micrologic Standard-function Trip Systems (LXL, LXIL) Circuit Breakers ...
Page 21
Neutral Current Transformers Catalogue Number Price Sensor LE25CT2 250 LE4CT2 400 LE6CT2 600 Neutral current transformers are required on 3Ø, 4W systems. Electronic Trip Indicator and Current Meter Field Installable Kits Device Catalogue No. Optional Local Trip ALTI LXL, LXIL ...
Page 22
Moulded Case Circuit Breakers Micrologic Trip Units Powerpact and Masterpact DE3-22 ® Powerpact circuit breakers may be specified with any of the following Micrologic Electronic Trip Units. Micrologic (Standard) 3.0 and 5.0 Trip Units • True RMS sensing • LI, ...
Page 23
P Frame - 1200A, Standard Rated MICROLOGIC Standard Trip Unit Amps MICROLOGIC 3.0 (LI Trip Functions) 250 400 600 800 1000 1200 MICROLOGIC 5.0 (LSI Trip Functions) 250 400 600 P-frame 3-pole 800 250–1200 Amperes 1000 1200 MICROLOGIC Ammeter Trip ...
Page 24
Moulded Case Circuit Breakers Powerpact Electronic Trip ® MICROLOGIC Trip Systems 80% Rated R-frame—2500 A, Standard Rated Micrologic Standard Trip Unit a Amps 3-pole, 600 Vac 50/60 Hz With LI Trip Functions (Micrologic 3.0) 600 800 1000 1200 1600 2000 ...
Page 25
P Frame - 1200A, 100% Rated G Interrupting Amps Catalogue Number MICROLOGIC 3.0 (LI Trip Functions) 250 PGL36025CU31A 400 PGL36040CU31A 600 PGL36060CU31A 800 PGL36080CU31A 1000 PGL36100CU31A 1200 PGL36120CU31A MICROLOGIC 5.0 (LSI Trip Functions) 250 PGL36025CU33A 400 PGL36040CU33A P-frame 3-pole 600 ...
Page 26
Moulded Case Circuit Breakers Powerpact Electronic Trip ® MICROLOGIC Trip Systems 100% Rated R-frame—2500 A, 100% Rated Micrologic Standard Trip Unit a Amps 3-pole, 600 Vac 50/60 Hz With LI Trip Functions (Micrologic 3.0) 600 800 1000 1200 1600 2000 ...
Page 27
Circuit breaker enclosures are UL Listed, CSA Certified and are suitable for use as service entrance equip- ment. The short circuit current rating of an enclosed circuit breaker is equal to the interrupting rating at the supply voltage marked on ...
Page 28
Moulded Case Circuit Breakers Enclosures—Accessories, Dimensions Accessories Insulated Groundable Neutral Assembly Circuit Breaker NEMA 1 & 3R Ampere Cat. No. Prefix Rating Cat. No. FAL, FHL, FCL 100 SN100FA FAL, FHL, FIL 100 — HDL,HGL,HJL,HLL 15–100 SN100FA HDL,HGL,HJL,HLL 125-150 SN400LA ...
Page 29
Electrical accessories are available on all moulded case circuit breakers except Q, QO Moulded Case Switches, and QOB-VH (125A - 150A). Factory installed accessories take up an additional pole space on QO, QOU, QO-GFI, QO-EDP and QO-PL circuit breakers. To ...
Page 30
Moulded Case Circuit Breakers Electrical Accessories Field Installed Complete field installable accessory catalogue number by inserting suffix from page DE3-29 in between the parenthe- ses in the catalogue numbers shown in the table below. For example, to order a 120V ...
Page 31
KAM02120AC WITH KAL Circuit Breaker Cylinder Lock Used to lock the breaker in the “OFF” position. Breaker cannot be reset when locked off. Breaker Catalogue Number Prefix Factory Inst. Field Inst. Price Suffix FA, FAL, Factory FH,FHL CL Installed KA, ...
Page 32
Moulded Case Circuit Breakers Accessories Used with HD, HG, HJ, HL, JD, JG, JJ, JL, DG, DJ, DL Circuit Breakers Rear Connections Device Description Poles Termination 2 Mixed Rear Connection Kit 3 Short rear connections (set ...
Page 33
Molded Case Circuit Breaker Electrical Accessories Accessory Description Shunt trip Trips the circuit breaker from a remote location by means of a trip coil energized from a separate circuit Undervoltage Trip Instantaneously opens the circuit breaker when its suppy voltage ...
Page 34
Moulded Case Circuit Breakers Accessories Used with PG, PJ, PK, PL, RG, RJ, RK, RL Circuit Breakers Adjustable Rating Plugs—Selection To provide maximum design flexibility, system protection, and field upgradeability, each Micrologic equipped with an interchangeable long-time rating plug. Each ...
Page 35
Trip unit field-installed accessories Description Unit Mount Circuit breaker Communication Module (BCM) S64205 6 Programmable Contacts Module (M6C) S64204 External Voltage SENSING (EVS) S64203 Electrical Accessories Description Shunt Trip or replacement of standard opening/closing coil for electrically operated P-frame Trips ...
Page 36
Moulded Case Circuit Breakers Accessories Used with MG, MJ, PG, PJ, PK, PL, RG, RJ, RK and RL Circuit Breakers Locking Accessories Circuit Factory-installed Catalogue Breaker Poles Suffix No. Prefix Toggle Padlocking Device—Removable M-, P-frame N/A S44936 ...
Page 37
Optional GFM25CT GFM250 ® The MICROLOGIC Ground Fault Module (GFM CSA certified and UL listed circuit breaker accessory combination ground fault relay and ground fault sensing device. The GFM is a self-powered ground fault sensing ...
Page 38
... Rectangular sensors 600:1 for GC-200E only. See Federal Pioneer Sensors (1000:1) for other versions (See Redi-Reference). DE3-38 GC-200 Ground Fault Relays work in conjunction with Square D and Federal Pioneer circuit breakers, with shunt trip coils, for use in service entrance switchboards, feeder protection and general equipment protection applications ...
Page 39
RH99M RH99P PA50 SA200 12/08 Moulded Case Circuit Breakers Ground-fault Protection Equipment Vigirex™ Ground-Fault Relay System The Vigirex ground-fault relays, with associated sensors (current transformers), measure the residual current in an electrical installation to detect levels which may be damaging. ...
Page 40
Moulded Case Circuit Breaker Operating Mechanisms Door Mounted Class 9421 Type L Circuit Breaker Operating Mechanism The Type L door mounted, variable depth operating mechanisms listed below are complete kits featuring heavy duty, all metal construction with trip indication. All ...
Page 41
... Handle mechanism A1 suitable for use on type 1, 3, 3R, 4 (sheet steel) & 12 enclosures. Handle mechanism A2 suitable for use on type 4 (stainless Steel) enclosures. Circuit Breaker Flexible Cable Mechanisms For use with Square D circuit breakers and Class 9422 A handle operators. Especially designed for tall, deep enclosures where placement flexibility is required. Circuit Breaker Type ...
Page 42
Moulded Case Circuit Breaker Terminals Used with HD, HG, HJ, HL, JD, JG, JJ, JL, DG, DJ, DL Circuit Breakers Mechanical Lug Kits Circuit Breaker Application Ampere Ampere Standard Optional Rating Rating Al Lugs for Use with ...
Page 43
Mechanical Lug Kit Information Standard Al Lugs for Use with Wire AL50FA AL100FA EDB, EGB, EJB EDB, EGB, EJB FA AL250KI AL250KA FC FA KA, KH AL400LA ...
Page 44
... Field-installable kits, including tin-plated aluminum PDC6FA6 connectors and all necessary mounting hardware are available for Square D FA, KA, LA, Q4, MA and P-frame molded case circuit breakers. • For use on load end of circuit breaker only • For use in UL508 Industrial Control applications only • ...
Page 45
... H- and J-frame Electronic Motor Circuit Protectors PowerPact H- and J-frame electronic Motor Circuit Protectors (MCP) are magnetic-only instantaneous-trip circuit breakers. They are designed to offer short circuit protection and are National Electrical Code (NEC) compliant when installed as part of a combination controller having motor overload protection. MCP circuit breakers accept the same accessories and terminals as the equivalent thermal-magnetic circuit breakers ...
Page 46
Moulded Case Circuit Breakers ® PowerPact H- and J-frame Electronic Motor Circuit Protectors Magnetic Trip Selection Table ® Application of PowerPact H-frame and J-frame Electronic Motor Circuit Protectors (MCP) Horsepower Rating of Induction-type Squirrel-cage and Wound-rotor Motors 3Ø ...
Page 47
... Adjustable Instantaneous Trip Circuit Breakers For Single Motor Circuit Protection Adjustable Instantaneous trip circuit breakers are intended for use in combination with motor starters with overload relays for the protec- tion of motor circuits from short circuits. Other specific applications include rectifiers and resistance welders. These C/B’s contain a mag- netic trip element in each pole with the trip point adjustable from the front ...
Page 48
... GARD circuit breakers comply with CEC requirements for providing motor circuit protection when installed as part of a listed combination controller having motor overload protection. Current interrupting ratings are established for these CSA recognized components in combination with motor starters with properly sized overload relays and contactors ...
Page 49
Figure 3 Figure 1 Figure Figure 5 Figure ...
Page 50
Moulded Case Circuit Breakers Dimensions and Shipping Weights Class 500, 600 Figure 16 Figure Figure 17 Figure 18 Figure 19 Figure 27 Figure 28 Figure ...
Page 51
Type 1 Provides Protection Against ... Accidental contact with enclosed equipment Dripping and light splashing of non corrosive liquids Limited amounts of falling dirt Windblown dust Rain, sleet, and external ice formation Hose directed water Corrosion Settling airborne dust, lint, ...
Page 52
... An expression related to energy (measured in ampere-squared seconds) that passes through an overcurrent protective device during an in- terruption. MAG-GARD®. The Square D family of instantaneous-trip circuit breakers (motor short-circuit protectors). moulded case circuit breaker. A circuit breaker that is assembled as an in- tegral unit in a supportive and enclosed housing of insulating material. ...
Page 53
A means of providing equipment ground- fault protection using sensors on each individual phase. root-mean-square (rms). The square root of the arithmetic mean of the squares of a set of numbers. rms current sensing. A method of ...