11-5-4 Setting Output Value for Errors
Description
Setting Patterns
Output Ranges and Values
Analog I/O Slave Unit (output) Functions
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
Low limit
High limit
Hold last state
Zero count
Note When a node address has been used more than once or a Unit error has
Output range
6. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
7. Click the OK Button and exit the window.
The value that is output when communications errors (time-out and BusOff
errors) occur can be set for each output. The four output settings are set using
the CX-Integrator.
occurred, the current output will be 0 mA and the voltage output will be 0 V,
regardless of the setting.
download the data, and then click the Reset Button to reset the Unit.
Outputs the values in the following table according to the output range.
Outputs the values in the following table according to the output range.
Holds and outputs the value from immediately before the error occurred.
Outputs the value when 0 is written from the Host. This setting will be
affected by scaling settings that are used.
–0.25 V
0.8 V
–0.5 V
–11 V
3.2 mA
0 mA
Low limit
5.25 V
5.2 V
10.5 V
11 V
20.8 mA
21 mA
High limit
Holds value.
Holds value.
Holds value.
Holds value.
Holds value.
Holds value.
Hold last state
Section 11-5
539