Specifications of NP-GEL70-12

Battery Capacity
71Ah
Battery Voltage
12V
Battery Technology
Lead Acid
External Height
207.01mm
External Width
169.164mm
External Depth
281.686mm
Weight
51.7lb
Battery Terminals
Bolt
Height
8.15"
Lead Free Status / RoHS Status
na
Nominal Voltage
Nominal Capacity
Float Charge Voltage
Cyclic Recharge Voltage
Internal Resistance (Fully Charged Battery)
Maximum Discharge Current
Operating Temperatures Range
Nominal Voltage
Nominal Capacity
Float Charge Voltage
Cyclic Recharge Voltage
Internal Resistance (Fully Charged Battery)
Maximum Discharge Current
Operating Temperatures Range
Shelf life and Storage
NP-GEL30-12
NP-GEL70-12
www.enersysinc.com
Performance Specifications
Range Summary
100
20 hour rate (1.3A to 10.50 volts)
10 hour rate (2.4A to 10.50 volts)
5 hour rate (4.7A to 10.20 volts)
1 hour rate (20.0A to 09.00 volts)
Charge
Discharge
20 hour rate (3.55A to 10.50 volts)
10 hour rate (6.80A to 10.50 volts)
5 hour rate (12.70A to 10.20 volts)
1 hour rate (53.00A to 09.00 volts)
Charge
Discharge
80
60
40
0
0
2
4
Standing Period (Months)
40
(104
o
6
C
o
F)
8
30
(86
10 12
o
C
o
F)
14 16 18 20
12 volts (6 cells in series)
26.0 A.H.
24.0 A.H.
23.5 A.H.
20.0 A.H.
13.5 Volts @ 77°F (25°C)
14.1-14.4 Volts @ 77°F (25°C)
9.4 milliohms (approx)
150A
-4°F (-20°C) to 122°F (50°C)
-4°F (-20°C) to 140°F (60°C)
12 volts (6 cells in series)
71.0 A.H.
68.0 A.H.
63.5 A.H.
53.0 A.H.
13.5 Volts @ 77°F (25°C)
14.1-14.4 Volts @ 77°F (25°C)
10 milliohms (approx)
150A
-4°F (-20°C) to 122°F (50°C)
-4°F (-20°C) to 140°F (60°C)
20
(68
o
C
o
F)
5
(41
o
C
o
F)
Charging is not
necessary unless
100% of capacity
is required.
Charging before
use is necessary
to help recover
full capacity.
Charge may fail
to restore full
capacity. Do not
let batteries reach
this state.
Nominal Voltage
Nominal Capacity
Float Charge Voltage
Cyclic Recharge Voltage
Internal Resistance (Fully Charged Battery)
Maximum Discharge Current
Operating Temperatures Range
Nominal Voltage
Nominal Capacity
Float Charge Voltage
Cyclic Recharge Voltage
Internal Resistance (Fully Charged Battery)
Maximum Discharge Current
Operating Temperatures Range
NP-GEL50-12
NP-GEL90-12
20 hour rate (2.50A to 10.50 volts)
10 hour rate (4.60A to 10.50 volts)
5 hour rate (8.80A to 10.20 volts)
1 hour rate (37.00A to 09.00 volts)
Charge
Discharge
20 hour rate (4.35A to 10.50 volts)
10 hour rate (8.20A to 10.50 volts)
5 hour rate (15.40A to 10.20 volts)
1 hour rate (63.00A to 09.00 volts)
Charge
Discharge
Publication No: US-NPGEL-RS-1 Feb 2003
12 volts (6 cells in series)
50.9 A.H.
46.0 A.H.
44.0 A.H.
37.0 A.H.
13.5 Volts @ 77°F (25°C)
14.1-14.4 Volts @ 77°F (25°C)
10 milliohms (approx)
150A
-4°F (-20°C) to 122°F (50°C)
-4°F (-20°C) to 140°F (60°C)
12 volts (6 cells in series)
87.0 A.H.
82.0 A.H.
77.0 A.H.
63.0 A.H.
13.5 Volts @ 77°F (25°C)
14.1-14.4 Volts @ 77°F (25°C)
10 milliohms (approx)
150A
-4°F (-20°C) to 122°F (50°C)
-4°F (-20°C) to 140°F (60°C)
3