SYSMAC BUS Master and Expansion Modules
The SYSMAC BUS Master and Expansion Modules provide
reliable remote I/O using G730 relay and transistor I/O blocks.
J SPECIFICATIONS
J CONFIGURATION
The following example shows one master and no expansions. The maximum system consists of one master and two expansion modules
per CQM1H CPU. Information on the G730 input and output blocks is shown in the Complementary Products section.
Item
Model
Description
Max. I/O points
Communications protocol
Communications method
Interface
Synchronization
Baud rate
Cable
Communications distance
Current consumption
A190
Transmission distance up to 200 m at 187.5 kbps
Reduce I/O wiring back to the controler to a single twisted
pair cable
Master modules connect up to 128 I/O; one master and two
expansions allowed per system
Use G730 transistor and relay input and output blocks shown
in the Complementary Products section
RS-485, 200 m max.
G730-VI (input model)
Switch
CQM1
Programmable Controller
Sensor
G730-VO (output model)
Specification
CQM1-G7M21
G730 remote master
64 max.
(32 inputs/32 outputs or
16 inputs/16 outputs, DIP
switch selectable)
Dedicated SYSMAC BUS protocol
Two-wire, half-duplex
RS-485
Start-stop
187.5 kbps
Two-conductor cable (VCTF 0.75 x 2 or Belden #9409 cable)
200 m max.
80 mA at 5 VDC
Master (32 input points/32 output points max.)
Lamp
CQM1H
CQM1- -G7M21 Master and CQM1-G7Nj1 Expansion
G730-RI (input model)
CQM1-G7N11
Input expansion module
32 max.
(32 or 16 inputs, DIP
switch selectable)
Switch
G730-RO (output model)
CQM1-G7N01
Output expansion module
32 max.
(32 or 16 outputs, DIP
switch selectable)
Valve