3-8 Installing the Controller Link Interface Unit
3-8-4
3-54
Wiring
Connecting the Communications Cable
This section describes the method for wiring the network communications cable to the Con-
troller Link Support Board.
Wire the communications cable to connect identical signals.
Connect the communications cable to the Controller Link Support Board after first connect-
ing it to the cable connector provided.
Use one of the twisted-pair cables listed below as the communications cable.
Reference
Li2Y-FCY2x0.56qmm KROMBERG & SHUBERT, De-
1x2xAWG-20PE+Tr.
CUSN+PVC
#9207
ESVC0.5x2C
ESNC0.5×2C-99-
087B
Precautions
for Safe Use
Precautions
for Safe Use
Wiring the Communications Cable
Model
Terminals for the same signal on the Controller Link Support Board’s connector are
connected internally.
The thickness of the ground wire connected to the Controller Link Support Board’s
connector must be less than 2.5 mm
Connect to the network using the special connector provided with the Controller Link
Interface Unit.
partment KOMTEC
DRAKA CABLES INDUSTRIAL
BELDEN
Bando Densen Co.
Nihon Electric Wire & Cable Co. Japanese company
• Use the cable specified for the communications cable.
• Keep communications cables separated from power lines or high-tension
• Ground the shield of the communications cable at one end of the network.
• Do not connect the shield cable of the communications cable to a ground
• Do not run wiring outdoors. If outdoor wiring is necessary, take protective
• Always turn OFF the power to PT before connecting the communications
• Use the connector attached to the Controller Link Support Board.
• Use the cables listed above.
• Normal communications may not be possible if a communications cable
lines to prevent influences from electronic noise.
Do not ground the shield at both ends.
that is also being used for power-system devices, such as inverters.
measures against lightening, such as underground wiring or wiring inside
pipes.
cable or installing/removing the connector.
other than those listed above is used.