Connecting to the RS-232C Port at the Host
68
RS-232 port
This is used mainly
for connection to the
RS-232C unit.
(This also supports
the CX-Programmer.)
Peripheral port
This is used mainly for
connection to the
Programming Device.
(This also supports the
RS-232C unit connection.)
Using the CPU Unit's Built-in RS-232C Port
*1
Using the CPU Unit's Peripheral Port
*1
When connecting PT with its model number 0, 2-5 to the built-in RS-232C
port, for example, set the value 8200 Hex to 160 CH, and 0005 Hex to 166CH.
Either set PLC Setup directly from a Programming Device (Programming Con-
sole), or transmit the PLC Setup made at a Programming Device (CX-Pro-
grammer) to the CPU Unit.
For details on the PLC Setup, refer to the SYSMAC CS Series Operation
Manual (W339) or the SYSMAC CJ Series Operation Manual (W393).
Setting the Front Switches
Set the CPU Unit’s DIP switch to 4 or 5 in accordance with the port NT631/
NT631C is connected to. An example of a CS-series CPU Unit is shown
below.
Connecting to CS-series Serial Communications Board
Serial Communications Board equipped with a RS-232C port for CS1-series
CPU Units: CS1W-SCB21(-V1)/41(-V1) (See note.)
166
150
160
161
144
145
Set any value between 0000 and 0009 Hex for the communications baud
rate. The same baud rate will be used regardless of the value as long as it
is between 0000 and 0009 Hex.
Set any value between 0000 and 0009 Hex for the communications baud
rate. The same baud rate will be used regardless of the value as long as it
is between 0000 and 0009 Hex.
Word #
Word #
SYSMAC CS1G
CPU42
PROGRAMMABLE CONTROLLER
PERIPHERAL
8200
0000 to 0009
000@
8200
0000 to 0009
000@
OPEN
RUN
ERR/ALM
INH
PRPHL/COMM
MCPWR
PORT
Writing Value
Writing Value
OPEN
BUSY
(*1)
(*1)
DIP switches (inside the battery storage)
• Set SW4 to ON (establishing communications in
• Set SW5 to OFF (establishing communications in
accordance with PLC Setup) when connecting the
NT631/NT631C to a peripheral port.
accordance with PLC Setup) when connecting the
NT631/NT631C to a peripheral port.
NT link (1:N) mode
Communications baud rate (standard)
@ = The largest model number of the con-
nected PT (0 – 7)
NT link (1:N) mode
Communications baud rate (standard)
@ = The largest model number of the con-
nected PT (0 – 7)
Settings
Settings
Section 4-1