Specifications of CRS1-RPT01

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Master Unit Specifications
Note: Communications power does not need to be supplied to the Master Unit.
Item
Applicable PLC
Unit classification
Current consumption (Power sup-
plied from PLC’s Power Supply Unit)
Communications power supply con-
nector
Communications power supply con-
nector allowable current capacity
Maximum number of mountable
Master Units
Mounting location
Communications power ON/OFF
monitoring
Data stored in Master Unit (built-in
EEPROM)
Noise immunity
Vibration resistance
Shock resistance
Dielectric strength
Insulation resistance
Ambient operating temperature
Ambient operating humidity
Ambient operating atmosphere
Storage temperature
Weight
Model
All CS-series PLCs
CS-series Special I/O Unit
400 mA max. at 5 VDC
One connector for the communications power supply is required for a Slave or Repeater Unit on the trunk line when using
Round Cable II, Flat Cable I, or Flat Cable II. (See note.)
5 A max. (4 A max. for UL rating)
When UL standards are being applied to your equipment, be sure the maximum allowable current is 4 A.
One word number assigned: 80 Units
Two word numbers assigned: 48 Units
Four word numbers assigned: 24 Units
Eight word numbers assigned: 12 Units
According to CS/CJ-series Special I/O Unit specifications.
The ON/OFF status of the communications power supply can be detected at the communications power supply connector.
1) The following device parameters:
2) Part of error history (depends on type of error; mainly serious error related to communications stopping)
Conforms to IEC 61000-4-4 2 kV (applied to PLC power supply).
10 to 61.2 Hz with single-amplitude of 0.1 mm, 61.2 to 150 Hz and 14.7 m/s
(sweep time of 8 min × 10 sweeps = 80 min)
196 m/s
500 VAC (between isolated circuits)
20 MΩ min. (between isolated circuits)
0 to 55°C
10 to 90% (no condensation)
No corrosive gases
−20 to 75°C
190 g max. (Master Unit only)
• Registration Table
• Registration Table Check Type
• Registered Slave Unit Participation Monitoring Time, Registered Slave Unit Participation Standby Mode, and Event
• Software Settings Table
• Manual I/O Communications Start Mode
• Communications Error Input Data Zero Clear Mode
• Network settings
Disable Setting
2
(3 times each in X, Y, and Z directions)
CS1W-CRM21
CS/CJ-series CompoNet Master Units
All CJ-series PLCs
CJ-series Special I/O Unit
One word number assigned: 40 Units
Two word numbers assigned: 40 Units
Four word numbers assigned: 24 Units
Eight word numbers assigned: 12 Units
130 g max. (Master Unit only)
CS1W/CJ1W-CRM21
2
in X, Y, and Z directions for 80 min each
CJ1W-CRM21
5