Minimizing Effects of a
Noisy Ground
2-2-11 Allocating Node Numbers
2-3
2-3-1
Available Cables
Cables, Connectors, and Related Devices
Thick Cable
Thin Cable
Cable
Cables, Connectors, and Related Devices
Communications Cables
Note
just that power supply’s to the shield wire and ground it. Do not connect the
shield wire at any other point.
1. Do not ground the shield wire at more than one point in the network.
2. Always use a separate ground. Never use the same ground that is used for
3. If a good ground of 100 Ω or less is not available, do not connect the com-
When the ground is identified as a source of noise in the network, disconnect
the DeviceNet shield wire to isolate it from the ground. If this step does not
stop noise from entering the network, do not ground the communications
power supply’s FG terminal.
Node numbers do not have to reflect the physical position of the nodes in the
network. It is possible to allocate node numbers randomly. It is also accept-
able to skip node numbers. While node numbers can be allocated randomly,
we recommend following a pattern when allocating node numbers. For exam-
ple, set the Master as node 63, the Slaves as nodes 1 through 62, and the
Configurator as node 0.
In a DeviceNet system, use DeviceNet cables that conforms to DeviceNet
specifications. The cable characteristics affect DeviceNet communications, so
cable that is not within DeviceNet specifications cannot be used. Always use
the specified DeviceNet cables.
There are two kinds of Special Thin/Thick Cable: Thick Cable and Thin Cable.
Thin Cable is used for the cables with attached shielded connectors.
Appearance
Ground the network at one point and one point only.
inverters or other drive system devices.
munication power supply’s FG and V- terminals because the ground may
introduce noise into the network.
DCA2-5C10
DCA1-5C10
Model
Outer diameter: 11.6 mm
Length: 100 m (See note.)
Outer diameter: 7 mm
Length: 100 m (See note.)