H3DE-F AC/DC24-230 Omron, H3DE-F AC/DC24-230 Datasheet - Page 20

TIMER DIN MNT 22.5mm

H3DE-F AC/DC24-230

Manufacturer Part Number
H3DE-F AC/DC24-230
Description
TIMER DIN MNT 22.5mm
Manufacturer
Omron
Series
H3DE-Fr
Datasheet

Specifications of H3DE-F AC/DC24-230

Relay Type
Integrated
Function
Interval
Circuit
SPDT (1 Form C)
Delay Time
0.1 Sec ~ 12 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24 ~ 230VAC/DC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Timing Adjustment Method
Screwdriver Slot
Timing Initiate Method
Input Voltage
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
H3DE-FAC/DC24-230
H3DEFACDC24230
■ Characteristics
Note: For reference:
Accuracy of operating time ±1% max. of FS
Setting error
Total tolerance of transfer
time
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Life expectancy
EMC
Degree of protection
Weight
A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1).
A maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
±10% ± 0.05 s max. of FS
± (25% FS + 5 ms) max.
±0.5% max. of FS
±2% max. of FS
100 MΩ min. at 500 VDC
Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60 Hz) for 1
min.
Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min.
Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min.
3 kV (between power supply terminals)
4.5 kV (between current-carrying metal parts and exposed non-current-carrying metal parts)
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 ms, 1-ns rise) ±1.5 kV
Malfunction: 4 kV
Destruction: 8 kV
Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Malfunction: 100 m/s
Destruction: 1,000 m/s
Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Electrical:
(EMI)
Emission Enclosure:
Emission AC Mains:
Harmonic Current:
Voltage Fluctuation and Flickering:
(EMS)
Immunity ESD:
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst:
Immunity Surge:
IP30 (IP20 for terminal block)
Approx. 120 g
100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
2
2
EN61812-1
EN55011 Group 1 class B
EN55011 Group 1 class B
EN61000-3-2
EN61000-3-3
EN61812-1
EN61000-4-2: 6 kV contact discharge (level 3)
EN61000-4-4: 2 kV power port and output port (level 3)
EN61000-4-5: 2 kV common mode (level 3)
8 kV air discharge (level 3)
1 kV control port with capacitive clamp (level 3)
1 kV differential mode (level 3)
H3DE-G