G3NA220BDC524 Omron, G3NA220BDC524 Datasheet

no-image

G3NA220BDC524

Manufacturer Part Number
G3NA220BDC524
Description
Relay SSR 7mA 32V DC-IN 20A 264V AC-OUT 4-Pin
Manufacturer
Omron
Datasheet

Specifications of G3NA220BDC524

Input Type
DC
Output Device
Triac
I/o Isolation Voltage
2500 V
Maximum Input Current
7 mA
Maximum Output Current
20@Ta=40C A
Maximum Input Voltage
32 V
Maximum Output Voltage
264 V
Output Type
AC
Input Voltage (max)
32V
Output Voltage (max)
264V
Input Current (max)
7mA
Output Current
20A
Isolation Voltage
2.5kV
Pin Count
4
Mounting
Screw
Operating Temp Range
-30C to 80C
Operating Temperature Classification
Commercial
Rad Hardened
No
Lead Free Status / RoHS Status
Compliant
New Models with 75-A and 90-A Output
Join the Previous Models with 5- to 50-A
Output.
• AC Output Relays with 75-A and 90-A output added.
• All models feature a uniform mounting pitch.
• Built-in varistor effectively absorbs external surges.
• Operation indicator enables monitoring operation.
• Protective cover for greater safety.
• Standard models certified by UL and CSA and -UTU mod-
Ordering Information
To Order: Select the part number and add the desired rated input voltage, (e.g., G3NA-240B-100 to 120 VAC)
.
Phototriac
Photocoupler
Phototriac
Photocoupler
Phototriac
Photocoupler
els by VDE (TÜV).
Solid State Relay
G3NA
(Table continued on next page.)
Isolation
Yes
Zero cross
function
Yes
Indicator
10 A at 24 to 240 VAC*
20 A at 24 to 240 VAC*
5 A at 24 to 240 VAC*
(19 to 264 VAC)
(19 to 264 VAC)
(19 to 264 VAC)
25 A at 24 to 240 VAC*
(19 to 264 VAC)
25 A at 200 to 480 VAC*
(180 to 528 VAC)
(applicable output load)
Rated output load
Solid State Relay
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
Rated input voltage
G3NA
G3NA-205B
G3NA-210B
G3NA-220B
G3NA-225B
G3NA-425B
Model
451

Related parts for G3NA220BDC524

G3NA220BDC524 Summary of contents

Page 1

... VAC 240 VAC* (19 to 264 VAC 240 VAC* (19 to 264 VAC 240 VAC* (19 to 264 VAC 200 to 480 VAC* (180 to 528 VAC) Solid State Relay Rated input voltage Model VDC G3NA-205B 100 to 120 VAC 200 to 240 VAC VDC G3NA-210B ...

Page 2

... DIN Rail Track (1.64 feet) length; use with Y92B-N❏❏❏ heat sinks DIN Rail Track (3.28 feet) length; use with Y92B-N❏❏❏ heat sinks Spacer End cap One-touch mounting plate G3NA 452 Solid State Relay Indicator Rated output load (applicable output load 240 VAC* (19 to 264 VAC 240 VAC* ...

Page 3

... VAC G3NA-475B-UTU 200 to 480 VAC 180 to 528 VAC G3NA-290B-UTU 24 to 240 VAC 19 to 264 VAC G3NA-490B-UTU 200 to 480 VAC 180 to 528 VAC *When the appropriate size OMRON heat sink is used. Operating Impedance voltage range (See note 1) Must operate voltage 7 mA max. ...

Page 4

... Storage -30° to 100°C (-22° to 212°F) with no icing Humidity 45% to 85% RH Weight Approx (2.1 oz.) Note: Data shown are of initial value. G3NA 454 Solid State Relay G3NA-240B G3NA-410B, G3NA- -420B, -425B, D210B -440B, -450B 1 ms max max. 1.6 V (RMS) 1.8 V (RMS 1 ...

Page 5

... Without heat sink 0 − − 100 Ambient temperature (°C) Solid State Relay G3NA-220B/420B With standard heat sink (Y92B-A100 or Y92B- N100) or aluminum plate measuring 200 mm x 200 With iron plate measuring 100 x 100 x t0 Without heat sink Ambient temperature (°C) G3NA-450B ...

Page 6

... Y92B-N100 1.99 Y92B-N150 0.45 Y92B-A100 0.45 Y92B-A150N Y92B-A250 Y92B-P250NF Note: When using a commercially available heat sink, use one with a 2.62 thermal resistance equal to or less that the OMRON Heat Sink. G3NA-240B G3NA-440B/-450B 400 300 200 100 0 500 1,000 5,000 10 ...

Page 7

... Input Note: When connecting the load, either the positive or negative side of the load terminals can be connected. Terminal Arrangement/ Internal Connections (Top View) Two, 4.3-dia holes Load Output 1 2 Load power supply (−) (+) 4 3 Input G3NA 457 Solid State Relay ...

Page 8

... G3NA 458 Solid State Relay To mount the Relay to DIN Track, first mount it to the One-touch Mounting Plate and then attach it to the DIN Track as shown in the diagram. To remove the Relay from the DIN Track, pull down on the tab with a screwdriver in the direction of the arrow ...

Page 9

... Fan power supply, 200 VAC 50/60 Hz 172 max. 160 max. 120 M4 110max. 47.6 Thermostat Two, M4 holes Weight: approx. 560 g NC contact, 90∞C Solid State Relay Mounting Holes Two, 4.4-dia holes 90±0.4 35±0.2 Weight: approx. 400 g Mounting Holes Two, 4.4-dia holes Weight: approx. 560 g ...

Page 10

... For surface mounting, a 30% derating of the load current is required (from the Load Current vs. Ambient Temperature graphs). The orientation indicated by the external dimensions is not the correct mounting orientation. When opening mounting holes, refer to the mounting hole dimensions. G3NA 460 Solid State Relay Mounting Holes 190.5 max. 70 max. Y92B-A250 Heat Sink ...

Page 11

... G3NA-440B G3NA-450B G3NA-D210B Note: 1. When used with the proper OMRON heat sink part number or an appropriately dimensioned equivalent. 2. The rated values approved by each of the safety standards (e.g., UL, CSA, and TÜV) may be different from the performance characteristics individually defined in this catalog the interest of product improvement, specifications are subject to change. ...

Page 12

... Precautions for Safe Use Although OMRON continuously strives to improve the quality and reliability of our relays, the G3NA contains semiconductors, which are generally prone to occasional malfunction and failure. ...

Page 13

... Size of fans Air volume: 0.7 m /min, Ambient temperature of control panel: 30 °C If there are other instruments that generate heat in the control panel other than SSRs, additional ventilation will be required. G3NA Solid State Relay Countermeasure 2 Duct Airflow Base Duct If the ducts cannot be shortened, place the SSR on a metal base so that it is not surrounded by the ducts ...

Page 14

... Heat Sink and mounting surface. Finally, tighten all four screws. G3NA 464 Solid State Relay Ratings and Characteristics of High- capacity Heat Sink (Y92B-P250NF) Fan Ratings Rated voltage ...

Page 15

... Load Load power supply Fuse model Manufacturer Applicable SSR 60LFF5 Kyosan Electric G3NA-205B Manufacturing 60LFF8 G3NA-210B Company 60LFF10 60LFF15 G3NA-220B 60LFF20 50SHA20 60PFF25 G3NA-240B 50SHA25 60PFF30 50SHA30 50SHA40 50SHA45 50SHA50 G3NA-275B-UTU 50SHA75 50SHA80 G3NA-290B-UTU 50SHB100 G3NA 465 Solid State Relay ...

Page 16

... G3NA. Switch element Snubber circuit Leakage current G3NA 466 Solid State Relay 3. Vibration and Shock Do not subject the G3NA to excessive vibration or shock. Otherwise the G3NA may malfunction and internal components may be deformed or damaged, resulting in failure of the G3NA to operate. To prevent the G3NA from abnormal vibration, do not install the G3NA in locations or by means that will subject it to vibration from other devices, such as motors ...

Page 17

... Seller within 30 days of receipt of shipment. III. PRECAUTIONS 1. Suitability THE BUYER’S SOLE RESPOINSIBILITY TO ENSURE THAT ANY OMRON PRODUCT IS FIT AND SUFFICIENT FOR USE IN A MOTORIZED VEHICLE APPLICATION. BUYER SHALL BE SOLELY RESPONSIBLE FOR DETERMINING APPROPRIATENESS OF THE PARTICULAR PRODUCT WITH RESPECT TO THE BUYER’ ...

Page 18

... THE OMRON PRODUCT IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Complete “Terms and Conditions of Sale” for product purchase and use are on Omron’s website at http://www.components.omron.com – under the “About Us” tab, in the Legal Matters section. ...

Related keywords