750104

Manufacturer Part Number
750104
Description
PNOZ S4 24 VDC
Manufacturer
PILZ
Datasheet

Specifications of 750104

Coil Voltage Vdc Nom
24V
Contact Current Max
8A
Contact Voltage Ac Nom
240V
Contact Voltage Dc Nom
24V
No. Of Poles
3
Relay Mounting
DIN Rail
External Width
22.5mm
External Depth
120mm
Svhc
No SVHC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
E-STOP relays, safety gate monitors
Up to PL e of EN ISO 13849-1
PNOZ s4
Function description
Timing diagram
Key
Wiring
Please note:
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
Single-channel operation: no re-
dundancy in the input circuit, earth
faults in the reset and input circuit
are detected.
Dual-channel operation without de-
tection of shorts across contacts:
redundant input circuit, detects
– earth faults in the reset and input
– short circuits in the input circuit
Dual-channel operation with detec-
tion of shorts across contacts: re-
dundant input circuit, detects
– earth faults in the reset and input
Power: Supply voltage
Reset/start: Reset circuit S34 S34
Input: Input circuits S11-S12, S21-
S22
Output safe: Safety contacts 13-14,
23-24, 33-34
Output aux: Auxiliary contacts 41-
42
Information given in the “Technical
details” must be followed.
Outputs 13-14, 23-24, 33-34 are
safety contacts, output 41-42 is an
auxiliary contact (e.g. for display).
To prevent contact welding, a fuse
should be connected before the
output contacts (see technical de-
tails).
Calculation of the max. cable runs
l
max
circuit,
and, with a monitored reset, in
the reset circuit too.
in the input circuit:
– short circuits in the input circuit
– shorts between contacts in the
Automatic start: Unit is active once
the input circuit has been closed.
Manual reset: Unit is active once
the input circuit is closed and then
the reset circuit is closed.
Monitored reset with falling edge:
Unit is active once
– the input circuit is closed and
– the reset circuit is closed and
Out semi: Semiconductor output
Y32
a: Input circuit closes before reset
circuit
R
ance (see technical details)
R
Use copper wire that can withstand
60/75 °C.
Sufficient fuse protection must be
provided on all output contacts with
capacitive and inductive loads.
lmax
l
: Automatic reset
: Manual reset
: Monitored reset with rising edge
: Monitored reset with falling edge
/km = cable resistance/km
circuit,
and, with a monitored reset, in
the reset circuit too,
input circuit.
then the reset circuit is closed
and opened again.
then opened again once the in-
= max. overall cable resist-
Monitored reset with rising edge:
Unit is active once the input circuit
is closed and once the reset circuit
is closed after the waiting period
has elapsed (see technical details).
Reset with start-up test: The unit
checks whether safety gates that
are closed are opened and then
closed again when supply voltage
is applied.
Increase in the number of available
instantaneous safety contacts by
connecting contact expander mod-
ules or external contactors/relays;
A connector can be used to con-
nect 1 PNOZsigma contact ex-
pander module.
b: Reset circuit closes before input
circuit
t
t
t
t
closed
1
2
3
4
: Switch-on delay
: Delay-on de-energisation
: Waiting period
: Waiting period reset circuit was
put circuit is closed.
NSG-D-2-395-2008-11