Specifications of PAXLR000

Count Rate
25kHz
Number Of Digits/alpha
6
Input Type
Logic, Transistor
Voltage - Supply
10 V ~ 16 VDC,115 VAC, 230 VAC
Display Type
LED
No. Of Digits / Alpha
6
Signal Input Type
Pulse
Character Size
0.56"
Ip/nema Rating
IP65 / NEMA 4X
Panel Cutout Height
1.77"
Display Font Color
Red
Panel Cutout Width
3.62"
Accuracy
±0.01% %
Connection Type
Cage-Clamp
Cut Out, Panel
3.62×1.77 "
Digit Height
0.56
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Function
Rate Indicator
Number Of Digits
6
Primary Type
Electronic
Range, Measurement
0.01 Hz to 25 kHz
Termination
Terminal Block
Voltage, Supply
115/230 VAC
Counter Supply Voltage
115/230VAC/10-16VDC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
RLC103
Installation
unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel
1.
2. POWER:
3. SENSOR POWER: 9 to 17.5 VDC @ 100 mA max.
4. KEYPAD: 3 programming keys, the ! (Down Arrow) key can also function
5. INPUT: (DIP switch selectable)
6. INPUT FREQUENCY RANGE:
7. MEMORY: Nonvolatile E
8. ENVIRONMENTAL CONDITIONS:
9. CERTIFICATIONS AND COMPLIANCES:
G
1.0 I
The PAX meets NEMA 4X/IP65 requirements when properly installed. The
DISPLAY: 6-digit, 0.56" (14.2 mm), 7-segment LED.
Decimal points are programmed by front panel keys.
AC Power: 115/230 VAC, switch selectable. Allowable power line variation
DC Power: 10 to 16 VDC @ 0.1 A max.
as the front panel reset button.
Accepts pulses from a variety of sources including NPN-OC, PNP-OC, TTL
Logic: Input trigger levels V
Current Sinking: Internal 7.8 KΩ pull-up to +12 VDC, I
Current Sourcing: Internal 3.9 KΩ pull-down, 8 mA max. @ 30 VDC max.
MAGNETIC PICK-UP:
Max Frequency: 25 KHz
Min Frequency: 0.01 Hz
Accuracy: ±0.01%
display values.
Operating Temperature: 0° to 60°C
Storage Temperature: -40° to 60°C
Operating and Storage Humidity: 0 to 85% max. relative humidity (non-
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
Shock According to IEC 68-2-27: Operational 30 g (10g relay), 11 msec in
Altitude: Up to 2000 meters
SAFETY
±10%, 50/60 Hz, 6 VA. @ 100 mA max.
Isolation: 2300 Vrms for 1 min. to input and DC Out/In.
Outputs, Magnetic Pickups and all standard Red Lion
Sensitivity: 200 mV peak
Hysteresis: 100 mV
Input impedance: 3.9KΩ @ 60 Hz
Maximum input voltage: ±40 V peak, 30 Vrms
condensing)
direction for 1.5 hours, 2g’s.
3 directions.
UL Recognized Component, File # E179259, UL61010A-1, CSA C22.2
No. 61010-1
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
ENERAL
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
NSTALLING THE
2
M
PROM retains all programmable parameters and
IL
= 1.5 V max.; V
ETER
gasket over the rear of the unit to the
back of the bezel. The unit should
be installed fully assembled.
Insert the unit into the panel
IH
cutout.
= 3.75 V min.
S
PECIFICATIONS
®
MAX
sensors.
= 1.9 mA
M
ETER
3
10. CONNECTIONS: High compression cage-clamp terminal block
11. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
12. WEIGHT: 12 oz (340 g)
so that the tabs of the panel latch engage in the slots on the case. The panel latch
should be engaged in the farthest forward slot possible. To achieve a proper seal,
tighten the latch screws evenly until the unit is snug in the panel (Torque to
approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
Installation Environment
operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.
keypad of the unit.
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for
Notes:
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage Capacity: 30-14 AWG copper wire.
Torque: 4.5 inch-lbs (0.51 N-m) max.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
While holding the unit in place, push the panel latch over the rear of the unit
The unit should be installed in a location that does not exceed the maximum
The bezel should be cleaned only with a soft cloth and neutral soap product.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
Immunity to Industrial Locations:
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
Surge
RF conducted interference
Power frequency magnetic fields
Voltage dip/interruptions
Emissions:
Emissions
IECEE CB Scheme Test Certificate # US/8843A/UL
Measurement, Control and Laboratory use.
1. Criterion A: Normal operation within specified limits.
2. EMI filter placed on the DC power supply, when DC powered: Corcom
CB Scheme Test Report # 04ME11209-20041018
IEC 61010-1, EN 61010-1:
IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529
#1VB3 or Schaffner #FN610-1/07 (RLC #LFIL0000).
Issued by Underwriters Laboratories, Inc.
equipment for measurement, control, and laboratory use, Part 1.
PANEL CUT-OUT
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8
EN 61000-4-11
EN 55011
Safety requirements for electrical
Criterion A
4 kV contact discharge
8 kV air discharge
Criterion A
10 V/m
Criterion A
2 kV power
2 kV signal
Criterion A
1 kV L-L,
1 kV signal
Criterion A
3 V/rms
Criterion A
30 A/m
Criterion A
0.5 cycle
Class B
2 kV L&N-E power
2
2