PAXLRT00 Red Lion Controls, PAXLRT00 Datasheet - Page 3

METER RTD TEMP 4-DIGIT

PAXLRT00

Manufacturer Part Number
PAXLRT00
Description
METER RTD TEMP 4-DIGIT
Manufacturer
Red Lion Controls
Series
PAX®LITEr
Type
RTDr
Datasheet

Specifications of PAXLRT00

Display Style
Red Characters, Black Background
Display Type
LED Red
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
4
Display Digits - Height
0.560" (14.22mm)
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
115VAC,230 VAC
Applications
RTD Input
Number Of Digits/alpha
4
No. Of Digits / Alpha
4
Meter Function
Temperature
Meter Range
-199.9°C To +850°C (-199.9°F To +999.9°F) / -200°C To +850°C (-328°F To +1562°F)
Digit Height
14.2mm
Power Consumption
6VA
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Other names
RLC115
1. DISPLAY: 4-digit, 0.56" (14.2 mm) high red LED, minus sign displayed for
2. POWER: 85 to 250 VAC, 50/60 Hz, 6 VA
3. CONTROLS: Three front panel push buttons for meter set-up. Rear terminal
4. RESOLUTION: 0.1 or 1 degree
5. RANGE: Decimal Point Dependent
6. OPEN/SHORTED RTD DETECTION: Display flashes: “
7. LEAD RESISTANCE EFFECT: 20  max., 2.5 °C/ error for V exc. and
8. ACCURACY: 0.3 °C, @ 23 °C and 30 min. warm-up
9. READING RATE: 2.5 readings/second
10. RESPONSE TIME: 2 seconds to settle for step input (increases with
11. LOW FREQUENCY NOISE REJECTION:
12. CERTIFICATIONS AND COMPLIANCES:
UNITS LABEL KIT (PAXLBK)
the Units Label Kit. The backlight is controlled in the programming.
the meter’s bezel display assembly.
G
A
negative temperatures.
Overrange/Underrange Input: Flashing “
Overrange/Underrange Display: “       ” or “
Isolation: 2300 Vrms for 1 min. between input and supply (300 V working
input for disabling the front panel.
common lead unbalance
programmable digital filtering)
Normal Mode Rejection: 40 dB @ 50/60 Hz (may be improved by
programmable digital filtering)
Common Mode Rejection: 120 dB, DC to 50/60 Hz
SAFETY
UL Recognized Component, File # E179259, UL61010A-1, CSA C22.2 No. 61010-1
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
IECEE CB Scheme Report # 04ME11209-20041018
Each meter has a units indicator with backlighting that can be customized using
Each meter is shipped with °F and °C overlay labels which can be installed into
voltage)
0.1° res: -199.9° to 850.0 °C (-199.9° to 999.9 °F);
1° res: -200° to 850 °C (-328° to 1562 °F)
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
IP65 Enclosure rating (Face only), IEC 529
CCESSORIES
ENERAL
Issued by Underwriters Laboratories, Inc.
for measurement, control, and laboratory use, Part 1.
M
ETER

      
” or “
S

PECIFICATIONS

” or “

3
Note:
13. ENVIRONMENTAL CONDITIONS:
14. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use. One
15. CONNECTIONS: High compression cage-clamp terminal block
16. WEIGHT: 0.65 lbs. (0.24 Kg)
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Operating Temperature Range: 0 to 50 °C
Storage Temperature Range: -40 to 80 °C
Operating and Storage Humidity: 85% max (non-condensing) from 0 to
50 °C
Span Drift: 50 ppm/ °C
Zero Drift: 0.001 °C/°C
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
Shock According to IEC 68-2-27: Operational 30 g’s, 11 msec in 3 directions.
Altitude: Up to 2000 meters.
piece bezel/case. Flame resistant. Panel gasket and mounting clip included.
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
Immunity:
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
Surge
RF conducted interference
Voltage dip/interruptions
Emissions:
Emissions
Control and Laboratory use.
1. Criterion A: Normal operation within specified limits.
direction for 1.5 hours, 2 g’s.
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
EN 55011
Criterion A
4 kV contact discharge
8 kV air discharge
Criterion A
10 V/m
Criterion A
2 kV power
2 kV signal
Criterion A
1 kV L-L,
1 kV signal
Criterion A
3 V/rms
Criterion A
0.5 cycle
Class B
2 kV L&N-E power