PAXLRT00 Red Lion Controls, PAXLRT00 Datasheet - Page 6

METER RTD TEMP 4-DIGIT

PAXLRT00

Manufacturer Part Number
PAXLRT00
Description
METER RTD TEMP 4-DIGIT
Manufacturer
Red Lion Controls
Series
PAX®LITEr
Type
RTDr
Datasheet

Specifications of PAXLRT00

Display Style
Red Characters, Black Background
Display Type
LED Red
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
4
Display Digits - Height
0.560" (14.22mm)
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
115VAC,230 VAC
Applications
RTD Input
Number Of Digits/alpha
4
No. Of Digits / Alpha
4
Meter Function
Temperature
Meter Range
-199.9°C To +850°C (-199.9°F To +999.9°F) / -200°C To +850°C (-328°F To +1562°F)
Digit Height
14.2mm
Power Consumption
6VA
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Other names
RLC115
sequence shown above, using the front panel push buttons.
From this mode, the user can restore the meter to factory default settings or
recalibrate the signal input if necessary. To prevent inadvertent entries, an
access code must be keyed-in to perform any operations in calibration mode.
terminal. With the PGM.DIS. terminal connected to RTD-, the meter displays
PROGRAMMING MODE ENTRY

PROGRAMMING MODE TIMEOUT
activity is detected for approximately 60 seconds, the meter automatically exits
Programming Mode. The meter briefly displays
display mode. When automatic timeout occurs, any changes that were made to
the parameter currently being programmed will not be saved.
PROGRAMMING PARAMETERS
current selection or value for that parameter. The dual display with arrows is
used below to illustrate the alternating display. The selection choices or value
range for each parameter is shown to the right of the alternating display.
the desired selection is displayed, press the PAR key to save the selection and
advance to the next parameter.
This setting does not change the Custom Units Overlay display (if installed).
Press the PAR key to save the selection and advance to the next parameter.
sets the display resolution to 1 or 0.1 degree. Press the PAR key to save the
selection and advance to the next parameter.
to compensate for probe errors or errors due to variances in probe placement, or
to adjust the readout to a reference thermometer. Set the desired display offset
value by pressing (and/or holding) the up or down arrow keys. When the desired
offset value is displayed, press the PAR key to save the selection and advance to
the next parameter. The display resolution for the offset value is the same as the
decimal point position programmed above.
4.0 P

The RTD Meter has seven programmable parameters that are entered in the
The last programming step offers the choice of entering calibration mode.
Note: Programming mode can be locked out using the Program Disable input
Press the PAR key to enter Programming Mode. The meter briefly displays
The Programming Mode has an automatic timeout feature. If no keypad
In Programming Mode, the display alternates between the parameter and the
Select the RTD type by pressing the up or down arrow keys ( or ). When
Select the desired temperature scale by pressing the up or down arrow keys.
Select the decimal point position by pressing the up or down arrow keys. This
The temperature display can be corrected with an offset value. This can be used
PAR
followed by the first programming parameter described below.
TEMPERATURE
” when the PAR key is pressed, and will not enter programming mode.



DISPLAY

Pro


TEMPERATURE DISPLAY OFFSET
ROGRAMMING THE
Type
RTD
rtd
DECIMAL POINT POSITION
TEMPERATURE SCALE
PAR



RTD TYPE
Temperature
SCAL
Scale
to



 
PAR

Decimal Point
PROGRAMMING SEQUENCE
Position
dCPt
and returns to the normal
PAR
Display Offset
Temperature
OFSt
M
PAR
6
ETER
Digital Input
If the temperature display is difficult to read due to small variations or noise,
increased levels of filtering will help to stabilize the display. Although the
digital filter features a “moving window” to help minimize response time,
higher levels of filtering will result in slightly longer response times.
Press the PAR key to save the selection and advance to the next parameter.
LO value for the entered delay time, the meter will capture the Input display as
the new HI or LO reading. A delay time helps to avoid false captures of sudden
short spikes or Input display variations that may occur during start-up.
Press the PAR key to save the selection and advance to the next parameter.
which can be installed in the meter bezel display assembly. The unit of measure
for the meter display is then visible when the label backlight is illuminated. The
two most commonly used temperature unit labels (°F and °C) are supplied with
the meter. Press the up or down arrow keys to select whether the units label
backlight is illuminated. Press the PAR key to save the selection and advance
to the next parameter.
Calibration Mode. To exit Programming Mode without entering Calibration
Mode, select
returns to the normal display mode. All programmed selections are now
transferred to non-volatile memory and are retained if power is removed from
the meter.
and reprogram, if necessary, when power is restored.)
Filtering
FLtr
This parameter sets the amount of digital filtering applied to the input signal.
Set the desired level of input filtering by pressing the up or down arrow keys.
When the Input display is above the present HI value or below the present
Set the desired capture delay time by pressing the up or down arrow keys.
The Units Label Kit Accessory contains a sheet of custom unit overlays,
Before exiting Programming Mode, The meter offers the choice of entering
(If power loss occurs during Programming Mode, verify parameter changes



PEAK (HI)/ VALLEY (LO) CAPTURE DELAY TIME

PAR



Capture Time
Peak/Valley
- no digital filtering
- normal filtering
and press the PAR key. The meter briefly displays
HL-t
PROGRAMMING MODE EXIT
UNITS LABEL BACKLIGHT
PAR
DIGITAL FILTERING


Units Label
Backlight
bLIt

PAR

- increased filtering
- maximum filtering
Mode Entry
Calibration
CAL

PAR
TEMPERATURE

DISPLAY
End
seconds

and