PAXLTC00 Red Lion Controls, PAXLTC00 Datasheet

METER THERMOCOUPLE 4-DIGIT

PAXLTC00

Manufacturer Part Number
PAXLTC00
Description
METER THERMOCOUPLE 4-DIGIT
Manufacturer
Red Lion Controls
Series
PAX®LITEr
Type
Thermocoupler
Datasheet

Specifications of PAXLTC00

Display Style
Red Characters, Black Background
Display Type
LED Red
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
4
Display Digits - Height
0.560" (14.22mm)
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
85 V ~ 250 VAC
Applications
Thermocouple Input - Type T, E, J, K, R, S, B, N, or mV
Number Of Digits/alpha
4
No. Of Digits / Alpha
4
Meter Function
Temperature
Digit Height
14.2mm
Power Consumption
6VA
Operating Temperature Range
0°C To +50°C
Supply Voltage Ac, Min
85V
Signal Input Type
Selectable Thermocouple
Accuracy
0.8 °C, 2.1 °C, 2.3 °C °C
Brand/series
PAXL Series
Connection Type
Cage-Clamp
Cut Out, Panel
3.62×1.77 "
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Display Resolution
1 °
Frequency
50⁄60 Hz
Function
Temperature
Number Of Digits
4
Primary Type
Electronic
Range, Measurement
-200 to +400 °C for T, -200 to +1000 °C for E, -200 to +760 °C for J, -200 to +1250 °C for K, 0 to +1768 °C for R, +150 to +1820 °C for B, -200 to +1300
Resolution
1 °
Standards
UL Recognized, CSA Certified, CE Approved
Temperature, Operating
0 to 50 °C
Temperature, Range, Measuring
-200 to +400 °C
Thermocouple Type
T
Voltage, Operating
85 to 250 VAC
Voltage, Supply
85 to 250 VAC
Character Size
0.56"
Display Font Color
Red
Rohs Compliant
NA
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
na, Contains lead / RoHS non-compliant
Other names
RLC116
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL PAXLTC - PAX LITE THERMOCOUPLE METER
GENERAL DESCRIPTION
and precisely linearizes them. A full 4-digit display accommodates a wide range
of temperature inputs. The unit automatically compensates for cold junction,
NBS linearity and the meter’s zero and span.
or 1 degree resolution. English Style display prompts and front panel buttons aid
the operator through set-up and operation. With a few simple steps the unit can
be used as a millivolt meter by selecting “
mode is useful in monitoring and displaying the actual voltage produced at the
thermocouple probe junction and as an aid in troubleshooting for a faulty
thermocouple probe.
selectable capture delay time. The capture delay is used to prevent detection of
false Peak or Valley readings that may occur during start-up or unusual process
events. The Peak and Valley readings are stored at power-down to allow
monitoring the process limits over any length of time (shifts, days, etc.).
up data is stored in EEPROM, which will hold data for a minimum of 10 years
without power. The meter has several built-in diagnostic functions to alert
operators of any malfunction.
the indicator extremely reliable in industrial environments. The front bezel
meets NEMA 4X/IP65 requirements for wash down applications.
C C
DIMENSIONS In inches (mm)
The Pax Lite Thermocouple Meter accepts inputs from standard thermocouples
The meter features a readout choice of either Fahrenheit or Celsius with 0.1
The meter provides a Peak (HI) and Valley (LO) reading memory with
Programmable digital filtering enhances the stability of the reading. All set-
Extensive testing of noise interference mechanisms and full burn-in makes
U L
R
8. 8 . 8 . 8
PAR
US LISTED
US LISTED
(96.5)
3.80
IND. CONT. EQ.
51EB
C
(49.5)
1.95

” for thermocouple type. This
(2.5)
.10
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" (53.4) H x 5" (127) W.
(104.1)
4.10
1
SAFETY SUMMARY
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired. Do not use this unit to directly
command motors, valves, or other actuators not equipped with safeguards. To
do so, can be potentially harmful to persons or equipment in the event of a fault
to the unit.
DEFINITION OF TERMS
 PROGRAMMABLE TC TYPE (T, E, J, K, R, S, B, N or mV SCALE)
 CONFORMS TO ITS-90 STANDARDS
 SELECTABLE °F OR °C WITH 0.1 OR 1 DEGREE DISPLAY
 STATE-OF-THE-ART DIGITAL ELECTRONICS FOR GREATER
 FULL 4-DIGIT, HIGH VISIBILITY, 0.56" (14.2 mm) HIGH RED LED
 PROGRAMMABLE TEMPERATURE OFFSET
 PROGRAMMABLE DIGITAL FILTERING ENHANCES STABILITY
 PEAK/VALLEY (HI/LO READING) MEMORY
 NEMA 4X/IP65 SEALED FRONT BEZEL
 CUSTOM UNITS OVERLAY WITH BACKLIGHT
All safety related regulations, local codes and instructions that appear in the
INSTALLATION CATEGORY (overvoltage category) I:
INSTALLATION CATEGORY (overvoltage category) II:
RESOLUTION
ACCURACY AND RELIABILITY
DISPLAY
instructions prior to installation
Signal level, special equipment or parts of equipment, telecommunication,
electronic, etc. with smaller transient overvoltages than Installation
Category (overvoltage category) II.
Local level, appliances, portable equipment, etc. with smaller transient
overvoltages than Installation Category (overvoltage category) III.
and operation of the unit.
CAUTION: Read complete
(44.5)
1.75
1
2
3
4
5 6
3.60 (91.4)
7
CAUTION: Risk of electric shock.
8
9
10
Bulletin No. PAXLTC-C
Drawing No. LP0572
Released 02/10
(44.5)
1.75

PAXLTC00 Summary of contents

Page 1

Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL PAXLTC - PAX LITE THERMOCOUPLE METER LISTED US LISTED R IND. CONT. EQ. 51EB GENERAL DESCRIPTION The Pax Lite Thermocouple Meter accepts inputs from standard ...

Page 2

T C ABLE OF ONTENTS Ordering Information . . . . . . . . . . . . . . . . . . . . 2 General Meter Specifications . . . . . . . . . ...

Page 3

G M ENERAL ETER 1. DISPLAY: 4-digit, 0.56" (14.2 mm) high red LED, minus sign displayed for negative temperatures. Overrange/Underrange Input: Flashing “  Overrange/Underrange Display: “       ” or “ 2. POWER ...

Page 4

I NSTALLING THE Installation The PAX meets NEMA 4X/IP65 requirements when properly installed. The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. ...

Page 5

EMC INSTALLATION GUIDELINES Although this meter is designed with a high degree of immunity to Electro- Magnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source ...

Page 6

P ROGRAMMING THE TEMPERATURE DISPLAY PAR Pro PAR PAR tYPE SCAL Thermocouple Temperature Type Scale The Thermocouple Meter has up to seven programmable parameters that are entered in the sequence shown above, using the front panel push buttons. Depending ...

Page 7

UNITS LABEL BACKLIGHT       The Units Label Kit Accessory contains a sheet of custom unit overlays, which can be installed in the meter bezel display assembly. The unit of measure for the meter display is ...

Page 8

... The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property ...