2864150 Phoenix Contact, 2864150 Datasheet - Page 7

no-image

2864150

Manufacturer Part Number
2864150
Description
DIN Rail Terminal Blocks MINI MCR-SL-UIUI-NC 3 WAY ISOLATING AMP
Manufacturer
Phoenix Contact
Type
Wire to Wirer
Datasheets

Specifications of 2864150

Product
DIN Rail Terminal Blocks
Current Rating
50 mA
Voltage Rating
30 V
Mounting Style
DIN Rail
Termination Style
Screw
Height
93.1 mm
Length
102.5 mm
Width
6.2 mm
Wire Gauge Max (awg)
12
Wire Gauge Min (awg)
26
Phoenix Part Number
MINI MCR-SL-UI-UI-NC
Supply Voltage
19.2 to 30 VDC
Temperature Range
–20°C to +60°C
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
MCR-SL-UI-UI-NC MINI
Power Supply
Feeding in power via the MINI Analog module
Where the total current consumption of the aligned
MINI Analog modules does not exceed 400 mA, the
power can be fed in directly at the connecting terminal
blocks of a MINI Analog module. We recommend con-
necting a 400 mA fuse upstream.
Feeding in power with a power terminal block
Power terminal block MINI MCR-SL-PTB
(Order No.: 28 64 13 4) of the same shape, or
MINI MCR-SL-PTB-SP (Order No.: 28 64 14 7) is
used to feed in the supply voltage to the DIN rail bus
connector. We recommend connecting a 2 A fuse
upstream.
Feeding in the power with a system power supply
unit
System power supply unit MINI-SYS-PS-...
(Order No.: 28 66 98 3) with 1.5 A output current
contacts the DIN rail bus connector with the supply
voltage, allowing several MINI Analog modules to be
supplied from the network.
101945_01_en
Never connect the supply voltage directly
to the DIN rail bus connector!
It is not permitted to draw power from the
DIN rail bus connector or from individual
MINI Analog modules!
Configuration
DIP switches S1 and S2 (see Figure 1, details 8
and 9) are used to define the combination of input and
output standard signal ranges (see
"Configuration Table" on page 8).
Standard Configuration
If it is an "NC version" (MINI MCR-SL-UI-UI-NC or
MINI MCR-SL-UI-UI-SP-NC), the device has the fol-
lowing standard configuration:
Input 0...10 V,
Output 0...20 mA,
All DIP switches in the "off" position,
Transmission error < 0.1%.
Electrostatic Discharge!
The module contains components that
can be damaged or destroyed by electro-
static discharge. When handling the mod-
ule, observe the necessary safety
precautions against electrostatic dis-
charge (ESD), in accordance with
EN 61340-5-1 and EN 61340-5-2, as well
as IEC 61340-5-1 and IEC 61340-5-2.
MINI MCR-SL-UI-UI(-SP)