SDV-FL4 DC100/110 Omron, SDV-FL4 DC100/110 Datasheet - Page 101

no-image

SDV-FL4 DC100/110

Manufacturer Part Number
SDV-FL4 DC100/110
Description
Sensor Hardware & Accessories VOLTAGE SENSOR
Manufacturer
Omron
Datasheets

Specifications of SDV-FL4 DC100/110

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Note: The range for an operating time of 0.3 s is 0.15 to 0.45 s and the range for an operating time of 0.8 s is 0.6 to 1.2 s.
Note: Do not connect ZCT output terminals k and l to ground. Doing so may result in damage to the Relay.
Item
Operating time
Inertial non-operating
time
Control power supply
range
Operating temperature
range
Operating humidity
range
Insulation resistance
Dielectric strength
Lightning impulse
dielectric strength
Lightning impulse
operation failure
Vibration resistance
Shock resistance
Rated current
Diameter of
through-hole
Rated voltage
Output terminal
polarity
Insulation
resistance
Dielectric strength
Ambient operating
temperature
Weight
Item
Ground Fault Relay Characteristics
ZCT (Zero-phase Current Transformer)
Structure
Model
Type
50 A
21 mm
600 VAC max., 50/60 Hz, single-phase/three-phase
None (The ZCT’s output terminals k and l can be connected to either input terminals 3 or 4 of the Relay.) (See note.)
100 M min. (between charged metal parts and ground)
2,200 VAC, 50/60 Hz for 1 min (between charged metal parts and ground)
Approx.
90 g
10 to 60 C (with no icing)
OTG-L21
Less than 0.1 s
---
80% to 110% of the control power supply voltage
45% to 85% (with no condensation)
5 M
1,500 VAC, 50/60 Hz for 1 min (between charged parts and the mounting panel)
1.2/50 s, 7,000 V (between control power supply terminals)
1.2/50 s, 7,000 V (primary side of ZCT)
Destruction: 16.7 Hz, 4-mm double amplitude for 1 min
98 m/s
10 to 55 C (with no icing)
min. at 500 VDC (between charged parts and the mounting panel)
2
High-speed models
100 A
30 mm
Approx.
130 g
OTG-L30
Indoor through-type models
200 A
42 mm
Approx.
230 g
OTG-L42
400 A
68 mm
Approx.
480 g
OTG-L68
0.3 s/0.8 s (switchable)
0.1 s when set to 0.3 s
0.5 s when set to 0.8 s
Delayed models
600 A
82 mm
Approx.
700 g
OTG-L82
1,000 A
156 mm
Approx.
6.6 kg
OTG-L156
Ground Fault Relay
200 A
52 mm
Approx.
1.3 kg
OTG-CN52 OTG-CN77
Less than 0.5 s
Delayed high-sensitivity models
Indoor separate-type models
400 A
77 mm
Approx.
2.5 kg
K6EL
600 A
112 mm
Approx.
3.5 kg
CN112
OTG-