SDV-SH5 Omron, SDV-SH5 Datasheet - Page 109

no-image

SDV-SH5

Manufacturer Part Number
SDV-SH5
Description
Sensor Hardware & Accessories SHUNT 5A
Manufacturer
Omron
Datasheets

Specifications of SDV-SH5

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Test Circuit
Select the resistance R shown in the test circuit diagram according to
the K6EL’s rated sensed current. Change the current using the slidac
and ascertain the K6EL’s operating value each time by reading the
ammeter.
For example, R could take the values shown below:
30 mA: 3.3 k , 6 W
100 mA: 1 k , 20 W
Precautions
Installation and Wiring
• Do not, under any circumstances, connect the ZCT’s output termi-
• Pass the primary conductor through the ZCT once.
• The Relay detects ground faults in internal wiring of devices due to
ZCT Installation
• Install the ZCT at an outdoor cable inlet or on a ground bus bar at a
• When installing on the electrical path, use a ZCT with a value
• If the secondary lines run in parallel to a circuit carrying a large cur-
• When installing a separate-type ZCT with current flowing along the
Switching the Sensed Current
1. With the K6EL-@100, 200, 500, R50, and R500, the sensed cur-
Separate by 20 cm min.
nals k and l to ground. Doing so may result in damage to the
Relay’s internal circuits.
insulation deterioration and so install the ZCT as close to the power
supply side as possible.
location allowing easy inspection.
greater than the electrical path’s rated current.
rent, either separate the lines as far as possible or use a shield line.
primary conductors, short the secondary terminals using clips or
some other method.
rent can be switched using a flat-bladed screwdriver.
Correct Use
ZCT
R
Slidac
Switch
Run the secondary lines
close to each other.
Ammeter
mA
Primary conductor
100 VAC
Circuit carrying large current
kt
lt
K6EL
OTC
k
l
K6EL
200 mA: 500 , 50 W
500 mA, 200 , 100 W
1,000 mA: 100 , 200 W
2. The sensed current for the K6EL-30 is fixed and hence cannot be
Switching the Operating Time
1. With the K6EL-A100, A200, and A500, the operating time can be
2. The operating time for the K6EL-30, 100, 200, 500, R50, and
Testing
• If the ground fault indicator (red) lights when the Relay’s test button
• To make an overall test, run a simulated ground fault current.
Resetting
• Once manual-reset models operate, they continue to operate until
• Automatic-reset models reset automatically when the ground fault
is pressed, it means that the internal circuits are operating nor-
mally.
they are reset. Reset them either by pressing the reset button
(black) or by turning the control power supply OFF and ON again.
is cleared (i.e., the current drops below the sensed current).
switched.
switched using a flat-bladed screwdriver.
R500 is fixed and hence cannot be switched.
Operating time selection switch
Sensed current selection switch
Ground Fault Relay
K6EL
107

Related parts for SDV-SH5