Output Circuits
Operation
Perform settings for the SAO Current Sensor and SET Current Converter in accordance with the current for the load used.
Current Settings
Note: The current range is determined by the number of conductor passes through the SET Current Converter and the tap setting. The range of
1. Current Sensor Settings
1. Current Scale Multiplying Factor
Determine the appropriate current scale multiplying factor for the cur-
rent setting range from the table, and attach the corresponding decal
to the Sensor. For example, for a current setting range of 2 to 5 A,
attach the 0.5 decal.
50
1 to 2.5
2 to 5
4 to 10
8 to 20
16 to 40
32 to 80
64 to 160
setting range)
Rated current
(current
the current scale on the Sensor is from 4 to 10 A and so attach a current scale multiplying factor decal (provided with the product) to the
Sensor if required.
Current Sensor (Single-phase)
0.25
0.5
1
2
4
8
16
multiplying factor
decal number
Current scale
Phase advancing
capacitor
SET-3
Current
Converter
Magnetic
contactor
Motor
R
M
8
4
2
1
1
1
1
Number of
conductor
S
passes
SAO-@S
Stop
pushbutton
Current Converter
SAO
Current
Sensor
Start
pushbutton
20
20
20
20
40
80
Fixed
Tap setting
BZ
6
7
Note: Provide the SAO Current Sensor’s control power
5
8
Alarm buzzer
SET-3A
SET-3B
4
1
supply from the contactor’s power supply side. If
the control power supply is turned ON at the
same time as motor start-up, the Sensor may
not operate in accordance with the time setting.