SDV-SH10 Omron, SDV-SH10 Datasheet - Page 21

no-image

SDV-SH10

Manufacturer Part Number
SDV-SH10
Description
Sensor Hardware & Accessories SHUNT 10A
Manufacturer
Omron
Datasheet

Specifications of SDV-SH10

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Safety Precautions
Approximately 0.5 s is required for operation. When confirming the
operating value, gradually change the input voltage while checking
the value.
Power supply voltage fluctuations and the ambient operating temper-
ature must be maintained within the allowable ranges. Be particularly
careful not to apply an overvoltage beyond the specified range for the
voltage detection.
Do not use the SDV in locations subject to corrosive or explosive
gases.
The SDV cannot be used to detect momentary power interruptions
because of its response time. Use the S87A to detect momentary
power interruptions.
An SDV cannot be used with a circuit containing thyristors, or VVVF
inverters, because these elements can change the output waveform
to the point that the SDV will malfunction.
Mounting
When mounting with the PL08 or PL15 Back Connection Socket,
insert the Socket into a 1- to 4-mm panel from the back and secure it
with screws. Do not mount the SDV until the Socket has been
mounted firmly. Be sure that the key groove on the Socket is
mounted on the bottom, and also secure the SDV to the panel with
screws.
When mounting with the 8PFA or 14PFA Back Connection Socket,
insert the SDV into the Socket and secure it with the hooks. Leave
approximately 30 mm or more between Sockets to allow enough
space for the hooks.
When mounting more than one SDV, allow at least 30 mm or more
between them.
S87A Power Interruption Detector
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.