E5CN-Q2MT500AC100240 Omron Automation, E5CN-Q2MT500AC100240 Datasheet - Page 11

no-image

E5CN-Q2MT500AC100240

Manufacturer Part Number
E5CN-Q2MT500AC100240
Description
Controller, Digital Temp, 48x48mm, Voltage Out, Thermoc In, 100-240VAC, 2Aux Out
Manufacturer
Omron Automation
Type
Temperaturer
Datasheet

Specifications of E5CN-Q2MT500AC100240

Brand/series
E5CN Series
Communication
USB
Dimensions
48mmW×48mmH×78mmD
Enclosure Rating
IP00, IP20, IP66
Height
2.28 in.
Input Type
RTD/Thermocouple
Ip Rating
IP00, IP20, IP66
Length
4.1 in.
Mounting Type
DIN Rail
Number Of Outputs
3
Output Type
Voltage
Primary Type
Controller
Resistance, Insulation
20 Megohms (Min.) @ 500 VDC
Special Features
USB Serial
Standards
UL, cULus, CSA
Temperature, Operating
-10 to +55 °C (Ambient)
Termination
Terminal Block
Thickness
1.89 in.
Voltage, Rating
100 to 240 VAC @ 50⁄60 Hz
Voltage, Supply
100 to 240 VAC
Supply Voltage
100-240 VAC or 24 VAC/VDC
Current Output
4-20 mA DC (E5CN-E5AN-E5EN)
Thermocouple Inputs
K, J, T, L, E, U, N, R, S, B
Platinum Rtd
Pt100 and JPt100
Infrared Sensor
10-70°C, 60-120°C, 115-165°C, 160-260°C
Voltage
0 to 50 mV
Lead Free Status / Rohs Status
RoHS Compliant part
External Connections
E5CN
Controllers
Option Units
E5CN-U
Note: For the Wiring Socket, purchase the P2CF-11 or PG3A-11 separately.
• A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
• Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.
do not connect any of the control output terminals to ground. (If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.)
Voltage output (for driving SSR)
Voltage output (for driving SSR)
Relay output
250 VAC, 3 A (resistive load)
12 VDC, 21 mA
Current output
Load: 600 Ω max.
12 VDC, 21 mA
Long-life relay output
250 VAC, 3 A (resistive load)
0 to 20 mA DC
4 to 20 mA DC
DO NOT
USE
Relay output
(three terminals used)
SPDT, 250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
Current output
CT2
CT1
Control output 2
12 VDC, 21 mA
4 to 20 mA DC
0 to 20 mA DC
Load: 600 W max.
E53-CNHH03N2
Communications
(RS-485) and CT2
E53-CNH03N2
Communications
(RS-485) and CT
Control output 1
Control output 1
RS-485
RS-485
CT1
A(−)
A(−)
B(+)
B(+)
11
12
13
14
15
11
12
13
14
15
mA
CT1
DO NOT
USE
DO NOT
USE
DO NOT
USE
EV2
DO NOT
USE
Analog input
RS-485
EV1
E53-CNHBN2
Event inputs
and CT
E53-CN03N2
Communications
(RS-485)
A(−)
B(+)
mA
DO NOT
USE
DO NOT
USE
Analog input
11
12
13
14
15
11
12
13
14
15
+
V
DO NOT
USE
V
+
Control output 1
Control output 1
DO NOT
USE
Control output 2
DO NOT
USE
+
+
TC/Pt
universalinput
DO NOT
USE
DO NOT
USE
DO NOT
USE
TC/Pt
universal input
EV2
E53-CNQ03N2
Communications
(RS-485) and
Control Output 2
RS-485
E53-CNBN2
Event inputs
B(+)
A(−)
+
EV1
A
B
B
A
B
11
12
13
14
15
B
11
12
13
14
15
External
power supply
EV2
Control output 2
Auxiliary outputs
(relay outputs)
Auxiliary output 2
Auxiliary output 1
E53-CNPBN2
Event Inputs and
External Power Supply
E53-CNQHN2
Control Output 2
and CT
EV1
DO NOT
USE
CT1
+
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
+
11
12
13
14
15
12 VDC,
20 mA
11
12
13
14
15
Auxiliary output
250 VAC, 3 A (resistive load)
(Relay outputs)
Auxiliary output 1
Auxiliary outputs (relay outputs)
250 VAC, 3 A
(resistive load)
Input power supply
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Auxiliary output 2
(Control output (cooling side))
External
power supply
DO NOT
USE
CT1
Control output 2
E53-CNPHN2
External Power
Supply and CT
E53-CNQHHN2
Control Output 2
and CT2
CT2
+
CT1
+
11
12
13
14
15
12 VDC,
20 mA
A heater burnout alarm, heater short alarm,
heater overcurrent alarm, or input alarm is
sent to the output to which the alarm 1
function is assigned.
11
12
13
14
15
An input error is sent to the
output to which the alarm 1
function is assigned.
E5CN/E5CN-U
External
power supply
E53-CNP03N2
Communications (RS-485)
and External Power Supply
E53-CNQBN2
Event Inputs and
Control Output 2
Control output 2
DO NOT
USE
EV2
RS-485
+
B(+)
A(−)
EV1
+
11
12
13
14
15
11
12
13
14
15
12 VDC,
20 mA