E5CN-Q2MT500AC100240 Omron Automation, E5CN-Q2MT500AC100240 Datasheet - Page 13

no-image

E5CN-Q2MT500AC100240

Manufacturer Part Number
E5CN-Q2MT500AC100240
Description
Controller, Digital Temp, 48x48mm, Voltage Out, Thermoc In, 100-240VAC, 2Aux Out
Manufacturer
Omron Automation
Type
Temperaturer
Datasheet

Specifications of E5CN-Q2MT500AC100240

Brand/series
E5CN Series
Communication
USB
Dimensions
48mmW×48mmH×78mmD
Enclosure Rating
IP00, IP20, IP66
Height
2.28 in.
Input Type
RTD/Thermocouple
Ip Rating
IP00, IP20, IP66
Length
4.1 in.
Mounting Type
DIN Rail
Number Of Outputs
3
Output Type
Voltage
Primary Type
Controller
Resistance, Insulation
20 Megohms (Min.) @ 500 VDC
Special Features
USB Serial
Standards
UL, cULus, CSA
Temperature, Operating
-10 to +55 °C (Ambient)
Termination
Terminal Block
Thickness
1.89 in.
Voltage, Rating
100 to 240 VAC @ 50⁄60 Hz
Voltage, Supply
100 to 240 VAC
Supply Voltage
100-240 VAC or 24 VAC/VDC
Current Output
4-20 mA DC (E5CN-E5AN-E5EN)
Thermocouple Inputs
K, J, T, L, E, U, N, R, S, B
Platinum Rtd
Pt100 and JPt100
Infrared Sensor
10-70°C, 60-120°C, 115-165°C, 160-260°C
Voltage
0 to 50 mV
Lead Free Status / Rohs Status
RoHS Compliant part
Terminal Cover
E53-COV17
Current Transformers
E54-CT1
E54-CT3
E54-CT3 Accessory
• Armature
• Plug
Approx. 6 dia.
Approx. 3 dia.
48.8
9.1
22
48
(22)
Note: The E53-COV10
18
cannot be used.
25
40 × 40
15
Connection Example
10
3
Plug
30
30
40
30
15
21
Two, M3 (depth: 4)
Waterproof Packing
Y92S-29 (for DIN 48 × 48)
5.8 dia.
12 dia.
Two, 3.5 dia.
Armature
10.5
Lead
2.36 dia.
2.8
7.5
9
Order the Waterproof Packing separately if it becomes lost or
damaged.
The Waterproof Packing can be used to achieve an IP66 degree of
protection.
(Deterioration, shrinking, or hardening of the waterproof packing may
occur depending on the operating environment. Therefore, periodic
replacement is recommended to ensure the level of waterproofing
specified in IP66. The time for periodic replacement depends on the
operating environment. Be sure to confirm this point at your site.
Consider one year a rough standard. OMRON shall not be liable for
the level of water resistance if the customer does not perform periodic
replacement.)
The Waterproof Packing does not need to be attached if a waterproof
structure is not required.
E54-CT3
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 120 A (50/60 Hz)
(Maximum continuous heater current for the
Temperature Controller is 50 A.)
Number of windings: 400±2
Winding resistance: 8±0.8 Ω
E54-CT1
Thru-current (Io) vs. Output Voltage
(Eo) (Reference Values)
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 400±2
Winding resistance: 18±2 Ω
100 mV
100 mV
100 μV
100 μV
100 V
100 V
10
10
10
10
10
10
1
1
1
1
1
1
50 Hz
50 Hz
10
10
E5CN/E5CN-U
100 mA
100 mA
500 Ω
1 kΩ
1 kΩ
1
1
RL = 10 Ω
100 Ω
Thru-current (Io) A (r.m.s.)
Thru-current (Io) A (r.m.s.)
50 Ω
R
100 Ω
L
10
10
= 10 Ω
1%
Distortion
factor 10%
3%
100 1,000 A
100 1,000 A
1%
3%
Distor-
tion
factor
10%
15