273-5-120 Time Mark Corporation, 273-5-120 Datasheet - Page 2

no-image

273-5-120

Manufacturer Part Number
273-5-120
Description
SINGLE PHASE CURRENT MONITOR 0.5 - 5 AMP
Manufacturer
Time Mark Corporation
Datasheet

Specifications of 273-5-120

Lead Free Status / Rohs Status
RoHS Compliant part
INSTALLATION
Using the Model 273 base diagram, pictured on the unit
(contacts shown in the de-energized condition), connect
operating voltage and current input wiring to the socket.
PIN DRAWING
ADJUSTMENT SETTINGS
The output contacts used will depend on whether the Model
273 is applied to detect over current, under current, to shut off
a load, or trip an alarm.
The internal relay will energize when the input current rises
above the Current Adjust setting. This allows the unit to be
set to detect over-current (relay will energize on fault). The
LED indicator will illuminate whenever the relay is energized.
Apply normal operating current, then adjust the Model 273
Monitor until the relay just trips or resets, depending on the
application. This will result in the unit tripping on relatively
small current changes.
NOTE:
of high humidity or contamination, it is recommended that the
base area and all exposed metal parts of the socket be coated
liberally with a good quality silicon grease, such as Dow Corning
DC-4 or DC-4X. Insert the unit into the socket and wipe off excess
grease around the base. This will prevent the entrance of moisture
Telephone: Main -
Fax:
E-mail:
Internet:
IN APPLICATIONS WHERE VOLTAGES IN EXCESS OF
300 VAC ARE TO BE MONITORED, BE CERTAIN TO USE
THE TIME MARK MODEL 51X120 8-PIN SOCKET, OR AN
EQUIVALENT UL APPROVED 600 VAC RATED SOCKET.
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE.
ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING.
MODEL 273
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 273.
When installing the Model 273 Current Monitor in areas
Sales - (800) 862-2875
sales@time-mark.com
http://www.time-mark.com
THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
CURRENT
SUPPLY
(918) 438-1220
(918) 437-7584
AC
WARNING
KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
4
5
6 7
3
2
Installation Instructions
8
1
Single Phase Current Monitor
and
GENERAL SAFETY
other
APPLICATION: Typical Under-current sensing
APPLICATION: Typical Over-current Alarm
TROUBLESHOOTING
Should the Model 273 Monitor fail to operate properly, check all
connections to the monitor, and to the control circuits. Verify that
the proper voltage and currents are present, and check all fuses.
WARRANTY
The Model 273 Single Phase Current Monitor is warranted to be
free from defects in materials and workmanship, and is covered by
our exclusive 5-Year Unconditional Warranty. If this device fails
to operate, for any reason, we will repair or replace it, free, for five
years from the date of purchase. Contact the Time Mark Sales de-
partment, Monday through Friday; 8 a.m. to 5 p.m., CST, for further
details.