Description
Sensor, Fiber-Optic; NPN; 12 to 24 VDC + 10% @ 10% Ripple (Max.); 150 mA (Max.)
Manufacturer
Omron Automation
Type
Fiber Opticr
Datasheet

Specifications of E3X-NM11

Case Material
PBT Plastic
Cover Material
Polycarbonate
Current, Consumption
150 mA (Max.)
Function
Fiber Optic
Mounting Type
Bracket/DIN Rail
Output
NPN
Primary Type
Photoelectric
Response Time
500 μs (Max.) @ Rated detection distance
Technology
Photoelectric
Temperature, Ambient
-25 to +55 °C (Operating)
Temperature, Storage
-40 to +70 ºC
Voltage, Supply
12-24 VDC
Control Output
NPN Open Collector
Enclosure Rating
IP50
Lead Free Status / Rohs Status
RoHS Compliant part

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
E3X-NM11
Manufacturer:
OMRON
Quantity:
475
E3X-N
J NO-OBJECT TEACHING
Note: 1. To detect dark objects in front of bright backgrounds, set the operation mode selector to D. ON.
J SENSITIVITY ADJUSTMENT
Combination of the E3X-NT/E3X-NM and Fine Through-beam Fiber Units (E32-T22S/T24S/T84S)
No-object Teaching
Press the teaching button once with no object in the sensing area.
Note: If detection is not stable after no-object teaching, perform
With/Without-object Teaching
Press the teaching button once with no object in the sensing area.
Procedure
1
2
3
4
5
6
2. If the set distance is very short (i.e., 0 to 12 mm for the E32-TC200 and 0 to 4 mm for the E32-DC200), no-object teaching is
3. If the teaching button is pressed for more than three seconds, the sensitivity of the E3X-Nj will be set to maximum, at which
4. The E3X-Nj will be ready to detect objects in approximately one second after the mode selector is set to RUN.
with/without-object teaching.
not possible due to excessive light, in which case, perform with/without-object teaching.
time the green indicator will be lit.
Operation
Locate the sensor head within the rated sensing range with the E3X-Nj.
Set the mode selector to TEACH.
The flashing function of the E3X-Nj will be activated. Therefore,
adjust the optical axes so that the tip of the emitting fiber will be lit. If
the optical axes are divergent, the tip of the emitting fiber will flash
and the built-in buzzer of the E3X-Nj will beep.
Press the teaching button for 0.5 to 2.5 seconds without a sensing
object. In the case the E3X-NM, select a channel with the channel
selector and press the teaching button, at which time the stability
indicator for the selected channel will flash.
The teaching indicator (red) is lit.
The built-in buzzer beeps once.
Set the mode selector to RUN. No-object teaching will be set when
the first sensing object passes through the sensing area.
The teaching indicator (red) turns green (automatically turned off in
one second).
Select the logical output required with the operation mode selector.
Object
8
E3X-NT
---
TEACH
TEACH
TEACH
RUN
RUN
L
D
ON
ON
E3X-NM
L ON
D ON
TEACH
TEACH
CH
TIMER
TIMER
RUN
RUN
SET
SET
1
TEACH
2 3 4
E3X-N

Related parts for E3X-NM11