Notice: Artisan Controls Corporation assumes no responsibilty for customer's applications or product design. The information and data contained herein
is the sole and exclusive property of Artisan Controls Corporation. Any duplication, misuse, or conversion of this information without the express written
consent of Artisan Controls Corporation is illegal and will result in damages including court costs and attorney fees being assessed against the party
misusing this property.
0.1 Seconds to
Artisan Controls Corporation
Parsippany, NJ
1024 Hours !
Time Delay Relay
www.artisancontrols.com
MODE : INTERVAL
MODEL : 2300SA-8
INPUT : 120VAC, 50/60Hz
RANGE : 0.1 SEC - 1024 HRS
5
4
2.4 MAX
3
6
Made in USA
2
7
8
1
0.1 0.2 0.4 0.8 1.6 3.2 6.4 12.8 25.6 51.2
Voltage
DIP Switch Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
1
1
1
Input
Solid State Timers and Controllers
2
2
2
2
0.6 MAX
1.8 MAX
3.6 MAX
3
4
4
4
4
8
8
8
Timing Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Time Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2300SA
Setting the time delay is an easy two step process :
Selecting the Time Range - Open or Close switches 11 & 12 per the chart
below to select from the four time ranges: 0.1 - 102.4 seconds, 1 - 1024
seconds, 1 - 1024 minutes, and 1 - 1024 hours.
Setting the Time Delay - The timer has a built-in delay equal to the switch
1 value for the selected range (0.1 sec, 1 sec, etc.). Close the additional
switches (1 - 10) which add their values from the chart below to the built-
in time to achieve the desired time delay.
Example: To set for 30 minutes - switches 11 closed and 12 open for
minutes range, then close switches 5, 4, 3, and 1 for a total of 29 minutes,
all other switches open. The built in 1 minute completes the full 30 minutes.
The 2300SA is an interval timer controlling a DPDT set of relay contacts.
The 2300SA is available in both AC and DC voltage models, and all
models provide an integral 12 position DIP switch used to determine the
time delay value. When the operating voltage is applied the unit energizes
the output relay and starts timing, at the end of the time delay the output
relay is de-energized. Remove the operating voltage to de-energize the
output relay and time delay. DIP switches 11 & 12 determine the time
delay range, while switches 1 - 10 determine the time delay period. The
integral LED indicates the state of the output contacts.
16
16
16
Operating
Voltage
Output
Contacts
5
32
32
32
6
64 128 256 512
64 128 256 512
64 128 256 512
7
Timing Period vs Timing Resistance Range
8
DELAY
9
ON
ON
10
ON
ON ON
11
off
off
ON
12
off
off
DIP Switch Adjustable
OFF
0.1 - 102.4 Seconds
Time Delay Range
1 - 1024 Seconds
1 - 1024 Minutes
Interval Timer
1 - 1024 Hours
DELAY