S3K2U2200-5 SOLA HEVI DUTY, S3K2U2200-5 Datasheet - Page 28

UPS - Uninterruptible Power Supplies 2200VA/1650W 230V

S3K2U2200-5

Manufacturer Part Number
S3K2U2200-5
Description
UPS - Uninterruptible Power Supplies 2200VA/1650W 230V
Manufacturer
SOLA HEVI DUTY
Datasheet

Specifications of S3K2U2200-5

Power Rating
2200 VA
Output Voltage Rating
230 V
Number Of Outlets
9
Interface Port
USB / SNMP
Runtime (full Load)
5 min
Runtime (half Load)
12 min
Topology
Line Interactive
Tower / Rackmount
Tower / Rackmount
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Figure 15 Battery mode at 61 – 80% battery capacity
Figure 16 Low Battery mode
7.4
When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds
every 10 seconds. As capacity decreases, fewer indicators remain illuminated. Figure 15 shows the
UPS in Battery mode with 61% - 80% battery capacity remaining.
When a low battery condition occurs, the Battery Indicator flashes green and the alarm sounds every
half-second. The default low battery warning is two (2) minutes but can be configured via MultiLink.
For more information, refer to 11.0 - Troubleshooting.
For approximate battery run times, refer to Table 6 - Battery run times. These run times are
approximates based on resistive load and an ambient temperature of 25°C (77°F). To increase this
time, turn Off non-essential pieces of equipment, such as idle computers and monitors, or add exter-
nal battery cabinets.
Battery Recharge Operation
Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger
begins recharging.
!
CAUTION
Turning Off the UPS while it is in battery mode will result in loss of output power.
22
Battery Indicator
illuminated
Battery Indicator
flashes green
Modes of Operation