Wiring
62
• LG is a noise-filtered neutral terminal. If noise is a significant source of
• If connecting the line ground and ground terminals, always ground both to
• The ground wire should not be more than 20 m long.
• The FQM1 is designed to be mounted so that it is isolated (separated)
• Do not share the FQM1's ground with other equipment or ground the
errors and to prevent electrical shocks, connect the line ground terminal
to the ground terminal and ground both with a ground resistance of less
than 100 Ω or less.
less than 100 Ω to prevent electrical shock.
from the mounting surface to protect it from the effects of noise in the
installation environment (e.g., the control panel).
FQM1 to the metal structure of a building. Doing so may worsen opera-
tion.
Control panel
FQM1
ground terminal
Ground the FQM1 system
separately to a resistance
of 100 Ω or less.