B401B System Sensor, B401B Datasheet

no-image

B401B

Manufacturer Part Number
B401B
Description
400 Series Plug-in Smoke Detectors
Manufacturer
System Sensor
Datasheet
400 Series Plug-in
Smoke Detectors
System Sensor’ s 400 Series plug-in smoke detectors
meet the performance criteria designated by
Underwriters Laboratories.
Features
• Low standby current
• Two visible LEDs “blink” in standby and provide a 360° field viewing
• Wide variety of mounting bases with built-in shorting spring
• Detector head plugs easily into base
• Built-in test switch
• Field sensitivity metering of detector to meet the requirements of
• Built-in tamper resistant feature
• SEMS screws for easy wiring
• Optional recessed mounting
• Removable cover and insect screen for field cleaning
Agency Listings
1451:
5451:
angle
NFPA 72
S2101
S911
OQ1AO.AY
OB3AO.AY
7271-1653:108
7270-1653:104
4271-91-EV.3
167-93-E
2185
The ion unit has a sensing chamber that is sealed from back pressure
air flow, dirt, and insects. This chamber is protected by a fine mesh
screen which can be cleaned or replaced. Additional key features
include a recessed mounting option, interchangeable ion, thermal
detectors, a variety of mounting bases, and a full line of optional
accessories.
Ionization. The 1451 ionization smoke detector includes a dual
source, dual unipolar detector chamber designed to sense the
presence of a broad range of smoke particles including those
produced by fast combustion as well as slow smoldering fires. This
chamber’s increased stability significantly reduces nuisance alarms
and provides better performance at higher air velocities.
Thermal. The Model 5451 thermal detector meets the needs
for applications where rapid response is vital and in locations
where rapid temperature increases would only be caused by a fire
emergency.
This detector contains a unique dual thermistor heat sensing circuit
that provides maximum performance and solid-state reliability. It
initiates an alarm in response to both rapid rate-of-rise conditions
(increases in excess of 15°F per minute) and fixed heat (135°F). This
enables the heat detector to communicate an alarm to the central
control panel prior to reaching its fixed set point for high rates of
rise, providing a timely response to both rapid and slow temperature
increases.

Related parts for B401B

B401B Summary of contents

Page 1

... Series Plug-in Smoke Detectors System Sensor’ s 400 Series plug-in smoke detectors meet the performance criteria designated by Underwriters Laboratories. Features • Low standby current • Two visible LEDs “blink” in standby and provide a 360° field viewing angle • Wide variety of mounting bases with built-in shorting spring • Detector head plugs easily into base • Built-in test switch • Field sensitivity metering of detector to meet the requirements of NFPA 72 • ...

Page 2

... Form A&C+A 120 VAC Max. Supervisory Form C 24 VDC 12 to 100** †† — 12/24 VDC 10 to 100** — 24 VDC † Flangeless base †† A lthough B401B and B401 bases are capable of operating at 12 and 24 VDC, they cannot be used with the 5451 applications Yes Yes Yes Yes Yes No No ...

Page 3

Wiring (–) (–) OPTIONAL (–) RA400Z RA400Z (– (+) 1 4 (+) (+) OPTIONAL FAULT TOLERANT WIRING 120 VAC (–) 3 RA400Z 2 4 (OPTIONAL (+) N. ...

Page 4

... Fixed heat detector with rate-of-rise. Alarm point at 57.2°C (135°F). Must be mounted to one of the 400 Series Bases listed in Mounting Base Guide. Accessories RA400Z Remote annunciator for 2- or 4-wire systems Use with ion and photo plug-in detectors. Fits standard U.S. single gang electrical box. B401BH Sounder base with B401. Requires an external 24 VDC power supply. Mounts square electrical box (1½ in minimum depth). MOD400R Detector sensitivity test tool. (See above.) Use with most analog or digital multimeters. Satisfies requirement of NFPA 72 for sensitivity testing. (See above.) RMK400 Recessed mounting kit for use with B401 or B401R mounting bases only ...