Functions
Characteristics:
pages 6 to 9
Time delay function block
Counter function block
Clock function block
Analogue function block
Functions
4
References:
pages 10 and 11
The Zelio Logic programmable relay comprises:
- 8 Time delay function blocks, each with 8 choices of parametering,
- 8 Counter function blocks,
- 8 Analogue function blocks, each with 7 choices of comparator parametering,
- 4 Clock function blocks, each comprising 4 channels.
TT p : time delay control input
RT p : time delay reset to zero
T p : time delay output
a: Zelio symbol/type of time delay
s: time base
t 00.00: time delay value
CC p : counting input
RC p : counter reset to zero
C p : counter output
DC p : count up/down selection
p: preset value
ABCD: time zones
MO 14: 32: current date and time
MO –>TH: first day/last day
ON: start time
OFF: off time
A4: analogue block output
Ref: reference voltage
IB ≤ Ref: type of operation available
value
: locking of time delay value
: locking of time zones
: locking of preset counter value
: locking of analogue block reference
: clock block output
“Zelio Logic”
programmable relays
Dimensions:
page 12
Programming example with 2 time zones
Channel A time zone
Channel B time zone
Schemes:
pages 12 and 13
When inputting data to the time delay
function block TT1, a window auto-
matically opens for the inputting of
the various parameters.
In the first programming line, each
pulse at input I1 increments or dec-
rements the counter C1.
Input I2 determines the counting
direction, either up or down.
The insertion of the clock block will
enable output Q1 to change state in
accordance with the preset time
zones.
From Monday to Friday, the active
time zone will be from 8: 00 (ON)
until 21: 00 (OFF).
For Saturday and Sunday, the active
time zone will be from 9: 00 (ON)
until 12: 00 (OFF)
The analogue function block controls
output Q 4 according to the result of
the comparison.
In this example, output Q 4 changes
state when the value of the analogue
input IC is greater than the 6.4 V
reference voltage.