SR1-A Schneider Electric, SR1-A Datasheet - Page 5

no-image

SR1-A

Manufacturer Part Number
SR1-A
Description
Zelio Logic programmable relays
Manufacturer
Schneider Electric
Datasheet
Characteristics
Approvals
Degree of protection
Temperature
Maximum relative humidity
Altitude
Mechanical resistance
Resistance to electrostatic discharge Immunity to electrostatic
Resistance to HF interference
Connection to screw terminals
(Tightened using Ø 3.5 screwdriver)
Programmable relay type
Primary
Voltage limits
Nominal frequency
Nominal input current
Heat dissipation
Micro-breaks
Isolation voltage
Protection
Programmable relay type
Number of control scheme
lines
Maximum cycle time
Response time (2)
Back-up time in case of power failure
Programme memory checking
(1) Minimum level under test conditions defined by the standards
(2) Time between change of state of an input and change of state of an output directly linked by the programme in the same cycle.
Presentation:
pages 2 to 5
Environmental characteristics
Supply characteristics
Processing characteristics
6
References:
pages 10 and 11
SR1-
Operation
Readability of display
Storage
Immunity to vibrations
Immunity to mechanical shock
discharge
Immunity to electromagnetic
radiated fields
Immunity to rapid,
pulsed transients
Immunity to surges
Immunity to damped
oscillatory waves
Flexible cable with cable end
Semi-rigid cable
Rigid cable
Tightening torque
Nominal voltage
Including ripple
Acceptable duration
Primary/earth
SR1-
Day/time
Programme and adjustments
“Zelio Logic”
programmable relays
Dimensions:
pages 12
˚C
˚C
˚C
m
mm
mm
mm
N.m
V
V
Hz
mA
W
Vrms
ms
ms
H
%
2
2
2
10.2...14.4
UL, CSA, C-TICK
IP 20
- 20...+ 55 conforming to IEC/EN 60068-2-1 and 60068-2-2
0...+ 55 conforming to IEC/EN 60068-2-1 and 60068-2-2
- 25...+ 70 (conforming to IEC/EN 61131-2)
95 without condensation or dripping water
0…2000
Conforming to standard IEC/EN 60068-2-6, test Fc
Conforming to standard IEC/EN 60068-2-27, test Ea
Conforming to standard IEC/EN 61000-4-2, level 3 (1)
Conforming to standard IEC/EN 61000-4-3, level 3 (1)
Conforming to standard IEC/EN 61000-4-4, level 3 (1)
Conforming to standard IEC/EN 61000-4-5
Conforming to standard IEC/EN 61000-4-12
1 conductor: 0.14…1.5, cable: AWG26…AWG16
2 conductors: 0.14…0.75, cable: AWG26…AWG18
1 conductor: 0.14…2.5, cable: AWG26…AWG14
1 conductor: 0.14…2.5, cable: AWG26…AWG14
2 conductors: 0.14…1.5, cable: AWG26…AWG16
0.6
B121JD
c 12
105
1.3
≤ 1 ms, repeated 20 times
Against polarity inversion
B121JD, p1ppBD, SR1-p101FU
60
6
12 to 24 (SR1-B121JD and
p1ppBD)
20 to 40 (SR1-p101FU)
≥ 72 to 40 ˚C
only applicable to SR1-B and SR1-E
For life, internal EEPROM
At each power-up
Schemes:
pages 12 and 13
p 1 p 1BD p 201BD B122BD p 101FU
c 24
19.2…30
83
1.6
130
2.9
45
1.1
p201BD, SR1-p201FU
80
8
14 to 26 (SR1-p201BD)
22 to 42 (SR1-p201FU)
a 100...240
a 85…264
50-60 (47...63)
a 100 V ≤ 50
a 240 V ≤ 27
3
≤ 10 ms, repeated 20 times
2000 (50-60 Hz)
Schneider Electric
p 201FU
a 100 V ≤ 80
a 240 V ≤ 40
5.3