25.5. I
The unit is designed to supply any kind of load, including unlimited capacitive and inductive loads.
25.6. S
The power supply can be put in series to increase the output voltage.
25.7. P
The power supply shall not be used in parallel to increase the output power.
25.8. P
Power supplies can be paralleled for 1+1 redundancy to gain a higher system availability. Redundant systems require
a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put
two C-Series power supplies in parallel. In case one power supply unit fails, the other one is automatically able to
support the load current without any interruption. This simple way to build a redundant system has two major
disadvantages:
-
-
This can only be avoided by utilizing decoupling diodes which are included in the decoupling module YR2.DIODE or
redundancy module YRM2.DIODE.
Recommendations for building redundant power systems:
a)
b)
c)
Nov. 2006 / Rev.1.1 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
The faulty power supply can not be recognized. The green LED will still be on since it is reverse-powered from
the other power supply.
It does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a -
virtually nearly impossible - case, the defective unit becomes a load for the other power supplies and the output
voltage can not be maintained any more.
Use separate input fuses for each power supply.
Monitor the individual power supply units. A DC-ok lamp and a DC-ok contact is included in the redundancy
module YRM2.DIODE. This feature reports a faulty unit.
When possible, connect each power supply to different phases or circuits.
Fig. 25-5 Schematic for series operation
NDUCTIVE AND
ERIES
ARALLEL
ARALLEL
AC
AC
O
Unit A
Unit B
PERATION
DC
DC
C–Series
U
U
SE TO
SE FOR
+
+
-
-
C
APACITIVE
I
www.pulspower.com Phone +49 89 9278 0
NCREASE
1+1 R
Earth
+
-
Load
EDUNDANCY
L
O
OADS
UTPUT
Instructions for use in series:
a)
b)
c)
d)
e)
Note: Avoid return voltage (e.g. from a decelerating motor or
battery) which is applied to the output terminals.
P
OWER
It is possible to connect as many units in series as needed,
providing the sum of the output voltage does not exceed
150Vdc.
Voltages with a potential above 60Vdc are not SELV any
more and can be dangerous. Such voltages must be installed
with a protection against touching.
For serial operation use power supplies of the same type.
Earthing of the output is required when the sum of the
output voltage is above 60Vdc.
Keep an installation clearance of 15mm (left/right) between
two power supplies and avoid installing the power supplies
on top of each other.
Germany
48V, 5A, S
INGLE
CS10.481
P
HASE
I
NPUT