f4-08thm Automation Direct, f4-08thm Datasheet - Page 2

no-image

f4-08thm

Manufacturer Part Number
f4-08thm
Description
Temperature Input Modules
Manufacturer
Automation Direct
Datasheet
e7–86
Temperature Input Modules
When you order the module, replace the "n" with the type of Thermocouple needed. For example, to order a Type
J thermocouple module, order part number F4-08THM-J or part number F4-08THM-K for a Type K module.
Number of channels
Input Ranges
Resolution
Input Impedance
Absolute Maximum
Ratings
Cold Junction
Compensation
Conversion Time
Converter Type
F4-08THM-n 8-Channel Thermocouple Input
PLC Products
8, differential inputs
Type B
Type C
Type E
Type J
Type K
Type R
Type S
Type T
12 bit (1 in 4,096)
27K
Fault protected input, 130 Vrms or 100VDC
Automatic
15ms per channel, minimum
1 channel per CPU scan
Successive Approximation, 574
-270/1372
-2: 0-100 mV
270/1000
529/1820°C
-210/760
-270/400
-1: 0-50 mV
65/2320
-3: 0-25mV
0/1768
0/1768
°
°
°
°
°
°
°
C,
C,
C,
C,
C,
C,
C,
-450/1832
-350/1390
-450/2502
984/3308°F
149/4208
-450/752
32/3214
32/3214
<--->
°
°
°
°
°
°
°
F
F
F
F
F
F
F
Linearity Error
Full Scale Calibration
Error
Maximum Inaccuracy*
PLC Update Rate
Digital Input Points
Required
Base Power Required 5V
Terminal Type (included)
External Power Supply
Operating Temperature
Storage Temperature
Accuracy vs Temperature*
Relative Humidity
Environmental Air
Vibration
Shock
Noise Immunity
Note 1: Terminate shields at the respective signal source
Note 2: Leave unused channels open (no connection)
Note 3: This module is not compatible with the ZIPLink wiring system.
± 1 count (0.03% of full scale) maximum
± 0.35% of full scale
± 1°C for type E, J, K, and T
± 3°C for type B, C, R, and S
1 ch. per scan min., 8 per scan max.
16 (X) input points (12 binary data bits,
3 channel ID bits, 1 sign bit)
120mA
Non-removable
24VDC ±10%, 50mA current
32 to 140°F (0 to 60°C)
-4 to 158°F (-20 to 70° C)
57 ppm/°C maximum full scale
5 to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
NEMA ICS3-304
*Max. inaccuracy is not guaranteed for
F4-08TM-n
temperatures lower than:
+100°C for types R & S
-220°C for types E & T
-200°C for types J & K
1 - 8 0 0 - 6 3 3 - 0 4 0 5