S8VS-06024B Omron, S8VS-06024B Datasheet - Page 25

POWER SUPPLY W/DISP 24VDC 2.5A

S8VS-06024B

Manufacturer Part Number
S8VS-06024B
Description
POWER SUPPLY W/DISP 24VDC 2.5A
Manufacturer
Omron
Series
S8VSr
Datasheets

Specifications of S8VS-06024B

Power Supply Type
Switching (Closed Frame)
Voltage - Output
24V
Number Of Outputs
1
Power (watts)
60W
Applications
Commercial
Voltage - Input
85 ~ 264VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 2.5A
Size / Dimension
4.26" L x 1.57" W x 3.74" H (108.3mm x 40mm x 95mm)
Power (watts) - Rated
60W
Operating Temperature
-10°C ~ 60°C
Efficiency
78%
Approvals
CE, CSA, cUL, EN, UL, VDE
Product
Switching
Output Power Rating
60 W
Output Voltage (channel 1)
24 V
Output Current (channel 1)
2.5 A
Dimensions
108.3 mm L x 40 mm W x 95 mm H
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
24V
Output Current
2.5A
Power Rating
60W
Input Voltage
85V AC To 264V AC
Length
108.3mm
Width
40mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S8VS06024B
Z1667
Undervoltage Alarm Function (Indication and
Output) (S8VS-@@@24A@@/S8VS-@@@24B@@/
S8VS-@@@24BE@ Only)
When output voltage drop is detected, an alarm (
output voltage value are indicated alternately. The preset value of
detection voltage can be changed in the setting mode.
(From 18.5 to 27.5 V in 0.1-V steps. The value is fixed at 20.0 V for
the S8VS-06024A/S8VS-06024B.)
Further, an output (undervoltage output terminal (DC LOW)) to an
external device is given from the transistor to notify of the error
(excluding S8VS-06024A/S8VS-06024B/S8VS-@@@24BE@).
(Output voltage drop = OFF, i.e., no continuity at the undervoltage
output terminal (DC LOW).)
Example: Outputting an Alarm When the Voltage Output by the
S8VS-09024A@@ Drops to the Set Value (19.0 V) or Lower
Note: 1. Operation begins after about three seconds since the AC
Note: Operation begins after about three seconds since the AC
AC input
Output
voltage
Undervoltage
output
Main display
2. The alarm is not indicated in the setting mode.
3. Press the
4. The undervoltage alarm function may also operate when an
5. The undervoltage alarm function monitors the output
power is supplied.
power is supplied.
restored, to reset alarm indication.
interruption in AC input is not restored within 20 ms.
terminal voltage of the Power Supply. To check the voltage
accurately, measure the voltage at the load end.
Operation
mode
(Mode Key (8)) after the output voltage is
Lowest value of
output voltage
In the case that the
output voltage drops
below the set value (19.0 V)
and an alarm is issued
a01
Voltage indication
) and lowest
Detection value
of Undervoltage
alarm
:
S8VS
25