TL100048 TDK Corporation, TL100048 Datasheet - Page 9

PWR SUP FNT END 48V 1000W 20A

TL100048

Manufacturer Part Number
TL100048
Description
PWR SUP FNT END 48V 1000W 20A
Manufacturer
TDK Corporation
Series
TLr
Datasheets

Specifications of TL100048

Power Supply Type
Switching (Closed Frame)
Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Voltage - Input
90 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 20A
Size / Dimension
11.12" L x 3.41" W x 3.45" H (282.4mm x 86.6mm x 87.6mm)
Power (watts) - Rated
1000W
Operating Temperature
-40°C ~ 65°C
Efficiency
92%
Approvals
CE, CSA, EN, UL
Line Regulation
±1%
Load Regulation
±1%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
20A
Power Rating
1000W
Input Voltage
90V AC To 264V AC
Length
282.448mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
285-1646
3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4
An individual feed architecture powers one power module on each AC feed. Connect the AC
source that is sized according to Table 5, Table 6, or Table 7, to the rear terminal block seen in
Figure 9. The tables are separated by system voltage, i.e. 12 volt, 24 volt, or 48 volt systems.
To size your AC feeds properly, use the tables below. Failure to size the AC breaker and wiring
properly can result in nuisance breaker trips or even damage to the equipment.
Follow the example below for determining AC breaker and wire sizing.
The tables below use the absolute minimum input voltage at which the power modules will run at
to determine AC requirements. 90 V corresponds to low line and 180 V corresponds to high line.
2.2.3 Sizing AC feeds
AC Line 1
AC Line 2
AC Line 3
AC Line 4
AC Line 5
Figure 3 - Individual Feed AC Wiring Architecture
TLR5-S S ERIES POWER SYSTEM
Revision A3 : July 2005
N+1 DC Out
Page. 9