TLR5-S S ERIES POWER SYSTEM
Figure 3 - Individual Feed AC Wiring Architecture
An individual feed architecture powers one power module slot per AC feed. Connect the feed,
sized according to section 2.2.3, into IEC320 plugs as seen in Figure 9. There are two different
types of individual AC feeds. The first type of AC connection is made with IEC320 connectors
that are rated for a maximum of 15 amps. Do not connect this type of individual AC system to
an AC breaker larger than 15 amps. The second type of AC connection is made with IEC320
connectors that are rated for a maximum of 20 amps. Do not connect this type of individual AC
system to an AC breaker larger than 20 amps. See section 2.2.2 for help determining your AC
architecture type.
2.3.3 Sizing AC feeds
To size your AC feeds properly, use Table 5, Table 6, and Table 7. Failure to size the AC breaker
and wiring properly can result in nuisance breaker trips or even damage to the equipment.
Follow the example below for determining AC breaker and wire sizing.
Use section 2.2.2 to determine the AC input type, for example a dual feed. Next determine the
number and model number of the power modules. Use Table 4 to determine the required AC
input voltage.
Page. 9
3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4
Revision 1 : January 2006