P7MF-06 Omron, P7MF-06 Datasheet - Page 9

SOCKET RELAY DIN RAIL FOR MKS-X

P7MF-06

Manufacturer Part Number
P7MF-06
Description
SOCKET RELAY DIN RAIL FOR MKS-X
Manufacturer
Omron
Series
MK-S(X)r
Type
Socketr
Datasheet

Specifications of P7MF-06

Number Of Positions
6
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Associated Relay Series
MKS-X
Mounting Style
DIN Rail
Width
78 mm
Accessory Type
Socket, Front Connecting
Socket Mounting
DIN Rail / Panel
Current Rating
15A
Socket Terminals
Screw
Voltage Rating
250VAC
Leaded Process Compatible
Yes
No. Of Poles
1
Rohs Compliant
Yes
For Use With/related Products
MK-S(X) Series
For Use With
Z2973 - RELAY PWR DC DPST-OC 5A 24VDCZ2972 - RELAY PWR DC DPST-OC 5A 120VACZ2971 - RELAY PWR DC DPST-OC 5A 24VDCZ2970 - RELAY PWR DC DPST-OC 5A 120VACZ2969 - RELAY PWR DC DPST-OC 5A 24VDCZ2968 - RELAY PWR DC DPST-OC 5A 120VACZ2967 - RELAY PWR DC DPST-OC 5A 24VDCZ2966 - RELAY PWR DC DPST-OC 5A 120VACZ2965 - RELAY PWR DC SPST-NO 10A 24VDCZ2964 - RELAY PWR DC SPST-NO 10A 120VACZ2963 - RELAY PWR DC SPST-NO 10A 24VDCZ2962 - RELAY PWR DC SPST-NO 10A 120VACZ2961 - RELAY PWR DC SPST-NO 10A 24VDCZ2960 - RELAY PWR DC SPST-NO 10A 12VDCZ2959 - RELAY PWR DC SPST-NO 10A 120VACZ2958 - RELAY PWR DC SPST-NO 10A 24VACZ2957 - RELAY PWR DC SPST-NO 10A 24VDCZ2956 - RELAY PWR DC SPST-NO 10A 12VDCZ2955 - RELAY PWR DC SPST-NO 10A 240VACZ2954 - RELAY PWR DC SPST-NO 10A 120VACZ2953 - RELAY PWR DC SPST-NO 10A 24VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
P7MF06
Z2990

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
P7MF-06
Manufacturer:
MOLEX
Quantity:
20
Safety Precautions
Be sure to read the precautions and information common to all electromechanical relays, contained in the Technical User’s Guide,
“Electromechanical Relays, Technical Information” for correct use.
Precautions for Correct Use
Installation
• Models for DC loads (i.e., models with “X” in the model number)
• Models for AC loads do not contain a permanent magnet.
• When mounting a P7MF-06(-D) Front-mounting Socket to a DIN
Gang Mounting
Conditions for mounting multiple MKS-X relays on the same DIN rail.
* Gang mounting of the Front-Mounting Sockets is not possible if the
Wiring
• The contact terminals on Models for DC Loads (i.e., models with “X” in
• Be sure to check plarity when wiring DC coil MKS-X relays with
Models for
DC Loads
Models for
AC Loads
contact carry current exceeds 10A.Provide space on both the right
and left sides of the Sockets.
The mounting pitch is given in the following diagram.
have permanent magnets built into the insulating block. If a
permanent magnet or other magnetic body comes near the Relay,
magnetic interference will occur with the built-in permanent magnet
and the contact switching capacity will be decreased.
Track, attach PFP-M End Plates on both sides of the Socket to
prevent it from moving.
the model number) have polarity. Wiring with incorrect polarity may
result in inability to turn OFF the Relay or loss of functionality.
built-in operation indicators.
Relay
20
15
10
5
0
0
10
10A
15A
Rated current
of Relay
20
Mounting interval (mm)
30
Mounting interval
Back-Connecting
40
Socket
50
Socket
Front-Connecting
Socket
*
General Purpose Power Relays
Operating Environment
Do not use the Relay in environments with combustible gas. Doing so
may result in explosion due to arcing.
Storage
Models for DC Loads (i.e., models with “X” in the model number) are
magnetized because they have a built-in magnet to deflect and
extinguish the arc. Do not install the Relay near IC cards or other
items that may be adversely affected by magnetism.
Usage
Use the Relay mounted in the P7M-06P or P7MF-06(-D) Socket.
Test Button
• Turn OFF the power supply before operating the test button. Always
• Do not use the test button as a switch.
• The durability of the test button is 100 operations minimum.
The circuit can be checked using either of two modes.
Test Button Applications
Example: Checking operation of Relays and sequence circuits.
return the test button to the original position after you use it.
(No tool is required.)
Press the button
Test Button
DC specification: Blue
AC specification: Red
for operation.
(momentary)
Mode 1
MKS-X
pressing down on the
Lock the contacts by
button and turning it.
(locked)
Mode 2
Normal
9

Related parts for P7MF-06