RELAY TIMER ANALOG DIN 4 MODE

H3DE-S2 AC/DC24-230

Manufacturer Part Number
H3DE-S2 AC/DC24-230
Description
RELAY TIMER ANALOG DIN 4 MODE
Manufacturer
Omron
Series
H3DEr

Specifications of H3DE-S2 AC/DC24-230

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.1 Sec ~ 120 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24 ~ 230VAC/DC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Timing Adjustment Method
Screwdriver Slot
Timing Initiate Method
Input Voltage
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption
Other names
H3DE-S2 AC/DC 24-230
H3DES2ACDC24230
Z1141
J TERMINAL ARRANGEMENT
Note: DC supply voltage does not require the designation of
J WIRING
The H3DE has a high impedance circuit. Therefore, the H3DE
may not be reset if the H3DE is influenced by inductive voltage.
In order to eliminate any influence of inductive voltage, the wires
connected to the H3DE must be as short as possible and should
not be installed alongside power lines. If the H3DE is influenced
by inductive voltage that is 30% or more of the rated voltage,
connect a CR filter with a capacitance of approximately 0.1 µF
and a resistance of approximately 120 Ω or a bleeder resistor
between the power supply terminals. If there is any residual
voltage due to current leakage, connect a bleeder resistor
between the power supply terminals.
Installation
polarity.
J OPERATION
An interval of 3 s minimum is required to turn on the H3DE after
the H3DE is turned off. If the H3DE is turned on and off
repeatedly with an interval of shorter than 3 s, the internal parts
of the H3DE may deteriorate and the H3DE may malfunction.
If it is required that the output be turned on repeatedly with an
interval of shorter than 3 s, consider use of the H3DE-M2/-M1 in
mode D (signal OFF-delay).
Power
Output
state 1
Output
state 2