H3DE-M2 AC/DC24-230 Omron, H3DE-M2 AC/DC24-230 Datasheet - Page 17

RELAY TIMER ANALOG DIN 8 MODE

H3DE-M2 AC/DC24-230

Manufacturer Part Number
H3DE-M2 AC/DC24-230
Description
RELAY TIMER ANALOG DIN 8 MODE
Manufacturer
Omron
Series
H3DEr
Datasheet

Specifications of H3DE-M2 AC/DC24-230

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.1 Sec ~ 120 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24 ~ 230VAC/DC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Timing Adjustment Method
Screwdriver Slot
Timing Initiate Method
Input Voltage
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption
Other names
H3DE-M2 AC/DC 24-230
H3DEM2ACDC24230
Z1139
Specifications
J GENERAL
Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm.
J TIME RANGES
Note: 1. Time scale display is applied commonly for ON and OFF time.
J RATINGS
Note: DC ripple rate: 20% max.
Item
Operating mode
Operating/Reset method
Terminal block
Terminal screw tightening torque
Output type
Mounting method
Attachment
Approved standards
Time scale display
(S
(See Note 1.)
x 0.1
x 1
Rated supply voltage (See Note.)
Operating voltage range
Power reset
Reset voltage
Power consumption
Control output
Ambient temperature
Ambient humidity
2. When the main dial is set to “0” for all settings, the output will operate instantaneously.
N
1 )
p y
Time unit display
sec
0.1 to 1.2 s
1 to 12 s
24 to 230 VAC/VDC (50/60 Hz)
85% to 110% of rated supply voltage
Minimum power-off time: 0.1 s
2.4 VAC/DC max.
AC: Approx. 3.1 VA (1.8 W) at 230 VAC
DC: Approx. 0.8 W at 24 VDC
Contact output: 5 A at 250 VAC with resistive load (cosφ = 1); 5 A at 30 VDC with resistive
load (cosφ = 1)
Operating: - -10°C to 55°C ( 14°F to 131°F) with no icing
Storage: - -25°C to 65°C (- -13°F to 149°F) with no icing
Operating: 35% to 85%
H3DE-F
Repeat-cycle with independent ON-time/OFF-time operation
Time-limit operation/Time-limit reset or self-reset
Clamps two 2.5 mm
0.98 N S m max. {approx. 10 kgf S cm max.}
Relay: SPDT
DIN track mounting (See Note.)
Nameplate
UL508, CSA 22.2 No.14
Conforms to EN61812-1, IEC60664-1 (VDE0110) 4 kV/2, VDE0106/P 100
Output category according to IEC60947-5-1
(AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A)
10 s
1 to 12 s
10 to 120 s
2
max. bar terminals without sleeves
min
0.1 to 1.2 min
1 to 12 min
hrs
0.1 to 1.2 h
1 to 12 h

Related parts for H3DE-M2 AC/DC24-230