H3DE-M2 AC/DC24-230 Omron, H3DE-M2 AC/DC24-230 Datasheet - Page 28

RELAY TIMER ANALOG DIN 8 MODE

H3DE-M2 AC/DC24-230

Manufacturer Part Number
H3DE-M2 AC/DC24-230
Description
RELAY TIMER ANALOG DIN 8 MODE
Manufacturer
Omron
Series
H3DEr
Datasheet

Specifications of H3DE-M2 AC/DC24-230

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.1 Sec ~ 120 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
24 ~ 230VAC/DC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Timing Adjustment Method
Screwdriver Slot
Timing Initiate Method
Input Voltage
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption
Other names
H3DE-M2 AC/DC 24-230
H3DEM2ACDC24230
Z1139
J CHARACTERISTICS
Note: For reference:
Accuracy of operating time
Setting error
Influence of voltage
Influence of temperature
Insulation resistance
Dielectric strength
Impulse withstand voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Life expectancy
EMC
Enclosure rating
Weight
A maximum current of 0.15 A can be switched at 125 VDC (cosφ=1).
A maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 100 mA at 5 VDC (failure level: P).
±1% max. of FS (±1% ±10 ms max. at 1.2-s range)
±10% ±0.05 s max. of FS
±0.5% max. of FS (±0.5% ±10 ms max. at 1.2-s range)
±2% max. of FS (±2% ± 10 ms max. at 1.2-s range)
100 MΩ min. at 500 VDC
Between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 VAC (50/60
Hz) for 1 min.
Between control output terminals and operating circuit: 2,000 VAC (50/60 Hz) for 1 min.
Between contacts not located next to each other: 1,000 VAC (50/60 Hz) for 1 min.
3 kV (or 1 kV for 24/48 VAC/VDC models) (between power supply terminals)
4.5 kV (or 1.5 kV for 24/48 VAC/VDC models) (between current-carrying metal parts and exposed
non-current-carrying metal parts)
Square-wave noise generated by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) ±1.5 kV (between
power supply terminals)
Malfunction: 4 kV
Destruction: 8 kV
Malfunction: 0.5-mm single amplitude at 10 to 55 Hz
Destruction: 0.75-mm single amplitude at 10 to 55 Hz
Malfunction: 100 m/s
Destruction: 1,000 m/s
Mechanical: 10 million operations min. (under no load at 1,200 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
EMI
Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Harmonic Current: EN61000-3-2
Voltage Fluctuation and Flickering EN61000-3-3
EMS
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 3);
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power port and output port (level 3);
1 kV control port with capacitive clamp (level 3)
Immunity Surge: EN61000-4-5: 2 kV common mode (level 3);
1 kV differential mode (level 3)
IP30 (IP20 for terminal block)
Approx. 120 g
2
(approximately 10G)
2
(approximately 100G)

Related parts for H3DE-M2 AC/DC24-230