XTAE007B10A001 EATON CUTLER HAMMER, XTAE007B10A001 Datasheet - Page 227

IEC Non-Reversing Starter

XTAE007B10A001

Manufacturer Part Number
XTAE007B10A001
Description
IEC Non-Reversing Starter
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of XTAE007B10A001

No. Of Phases
Single Or Three
Power Rating
3.5kW
Current Rating
7A
Operating Temperature Range
-25°C To +50°C
Mounting Type
DIN Rail
Overload Adjustment Current Max
1A
Overload Adjustment Current Min
0.6A
Supply Voltage Max
120VAC
Frame Size
Standard
400, 415V Type 2 Coordination—Contactor with
Circuit Breaker
P
(kW)
1.50
2.20
3.00
4.00
5.50
7.50
11.0
15.0
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0
110.0
132.0
160.0
200.0
250.0
Magnet Coil Suffix
Frames A–B
Coil Voltage
110V 50 Hz, 120V 60 Hz
220V 50 Hz, 240V 60 Hz
230V 50 Hz
24V 50/60 Hz
24 Vdc
415V 50 Hz, 480V 60 Hz
550V 50 Hz, 600V 60 Hz
208V 60 Hz
190V 50 Hz, 220V 60 Hz
240V 50 Hz, 277V 60 Hz
380V 50 Hz, 440V 60 Hz
400V 50 Hz
380V 60 Hz
12V 50/60 Hz
24V 50 Hz
42V 50 Hz, 48V 60 Hz
48V 50 Hz
120 Vdc
220 Vdc
12 Vdc
48 Vdc
I
(A)
3.60
5.00
6.60
8.50
11.3
16.0
21.7
29.3
36.0
41.0
55.0
68.0
81.0
99.0
134.0
161.0
196.0
231.0
279.0
350.0
430.0
e
Suffix Code
A
B
F
T
TD
C
D
E
G
H
L
N
P
R
U
W
Y
AD
BD
RD
WD
I
(kA)
50
50
50
50
50
50
50
50
50
50
50
80
80
80
80
80
80
70
70
70
70
q
Circuit
Breaker—MCP
HMCPE015E0C
HMCPE015E0C
HMCPE015E0C
HMCPE015E0C
HMCPE015E0C
HMCPE015E0C
HMCPE100R3C
HMCPE100R3C
HMCPE100R3C
HMCPE100R3C
HMCPE100R3C
HMCPJ250D5L
HMCPJ250F5L
HMCPJ250G5L
HMCPJ250J5L
HMCPJ250W5L
HMCPJ250W5L
HMCPL600R
HMCPL600X
HMCPL600P
HMCPL600M
Frames C–F
Coil Voltage
110V 50 Hz, 120V 60 Hz
220V 50 Hz, 240V 60 Hz
230V 50 Hz
24V 50/60 Hz
24–27 Vdc
415V 50 Hz, 480V 60 Hz
550V 50 Hz, 600V 60 Hz
208V 60 Hz
190V 50 Hz, 220V 60 Hz
240V 50 Hz, 277V 60 Hz
380V 50 Hz, 440V 60 Hz
400V 50 Hz
380V 60 Hz
12V 50/60 Hz
24V 50 Hz
42V 50 Hz, 48V 60 Hz
48V 50 Hz
110–130 Vdc
200–240 Vdc
12–14 Vdc
48–60 Vdc
Volume 5—Motor Control and Protection CA08100006E—May 2011 www.eaton.com
Contactor
Catalog Number
XTCE018C10_
XTCE018C10_
XTCE018C10_
XTCE018C10_
XTCE018C10_
XTCE018C10_
XTCE040D00_
XTCE040D00_
XTCE040D00_
XTCE050D00_
XTCE065D00_
XTCE080F00_
XTCE095F00_
XTCE115G00_
XTCE150G00_
XTCE185L22_
XTCE225L22_
XTCE300M22_
XTCE300M22_
XTCE400M22_
XTCE500M22_
Suffix Code
A
B
F
T
TD
C
D
E
G
H
L
N
P
R
U
W
Y
AD
BD
RD
WD
IEC Contactors and Starters
480V Type 2 Coordination—Contactor with
Circuit Breaker
P
(hp)
50.0
60.0
150.0
200.0
250.0
300.0
350.0
Frame G
Coil Voltage
100–120V 50/60 Hz
190–240V 50/60 Hz
24V 50/60 Hz
24–27 Vdc
480–500V 50/60 Hz
380–440V 50/60 Hz
42–48V 50/60 Hz
110–130 Vdc
200–240 Vdc
48–60 Vdc
Wye-Delta (Star-Delta) Applications
If Type 2 Coordination is
required when using wye-
delta starters, the full voltage
(direct on-line) test data that
is included in this document
is valid. To ensure proper
Notes
For use with magnetic sensing means to monitor motor current.
Underscore (_) indicates magnet coil code required. See magnet coil suffix tables on
this page.
With DC operation: integrated diode-resistor combination, coil rating 2.6W.
I
(A)
65.0
77.0
180.0
240.0
300.0
361.0
414.0
e
XT IEC Power Control
Suffix Code
A
B
T
TD
C
L
W
AD
BD
WD
I
(kA)
65
65
50
50
50
50
50
q
Circuit
Breaker—MCP
HMCPJ250G5L
HMCPJ250G5L
HMCPL600N
HMCPL600N
HMCPL600R
HMCPL600Y
HMCPL600M
Frames L–M
Coil Voltage
110–250V 40–60 Hz/DC
250–500V 40–60 Hz/DC
48–110V 40–60 Hz/DC
24–48 Vdc
protection, the K1M (main),
K3M (star) and K5M (delta)
contactors must all be the
same size (amperage). For
wye-delta starter kits, please
see Page V5-T27-56.
Contactor
Catalog Number
XTCE080F00_
XTCE080F00_
XTCE300M00_
XTCE300M22__
XTCE300M22_
XTCE400M00_
XTCE500M00_
27.1
Suffix Code
A
C
Y
TD
V5-T27-227

Related parts for XTAE007B10A001