ESX10-124-DC24V-10A E-T-A Circuit Protection and Control, ESX10-124-DC24V-10A Datasheet - Page 5

no-image

ESX10-124-DC24V-10A

Manufacturer Part Number
ESX10-124-DC24V-10A
Description
CIRCUIT PROTECTOR; 10 A CLASS I, DIVISION 2 ; RESET INPUT AND STATUS OUTPUT ; 24
Manufacturer
E-T-A Circuit Protection and Control
Type
Electronicr
Datasheet

Specifications of ESX10-124-DC24V-10A

Actuator Type
Toggle
Brand/series
ESX10
Current, Rating
10 A
Mounting Type
Plug-In
Number Of Poles
1
Termination
Blade
Voltage, Rating
24 VDC
Lead Free Status / Rohs Status
RoHS Exempt Product
Issue C
Reliable trip of ESX10 with different cable lengths and cross sections
Resistivity of copper ρ
U
ESX10-selected rating I
e. g. trip current I
R
Example 1:
Example 2:
Example 3:
*1)
S
max
current limitation typically 1.8 x I
current limitation typically 1.5 x I
current limitation typically 1.3 x I
= DC 19.2 V (= 80 % v. 24 V)
10000
1000
0.01
100
in Ohm = (U
0. 1
10
5
1
0
disconnection
typically 1.1 x I
ab
S
Electronic Circuit Protector ESX10
= 1.25 x I
/ I
1
ab
0
max. length at 1.5 mm
max. length at 1.5 mm
mixed wiring:
(Control cabinet – sensor/actuator level) R1 = 0.95 Ohm, R2 = 0.71 Ohm
N
cable length L in meter
(= single length)
Cable cross section A in mm
) - 0.050
=
(in A)
The ESX10 reliably trips from 0 Ohm to max. circuitry resistance R
N
N
1.8 x I
(in A)
typically 1.8 x I
current limitation
N
N
N
2
N
times rated current at I
times rated current at I
times rated current at I
*1)
...times rated current
Time/Current characteristic curve (T
N
3
5
10
15
20
25
30
35
40
45
50
75
100
125
150
175
200
225
250
2
2
*1)
and 3 A
and 6 A
Table 3: Reliable trip of ESX10
cable resistance in Ohm = (R
2
3.75
5.07
3
0.0178 (Ohm x mm
voltage drop of ESX10 and tolerance of
trip point (typically 1.1 x I
N
N
N
4
= 8 A or 10 A
= 0.5 A...6 A
= 12 A
www.e-t-a.com
2.51
1.27
2.54
3.81
5.09
6.36
7.63
8.90
10.17
11.44
12.71
19.07
25.34
31.79
38.14
44.50
50.86
57.21
63.57
7.5
R1 = 40 m in 1.5 mm
0.14
6
5
214 m
106 m
IK
2
The trip time is typically 3 s in the range between 1.1 and 1.8 x I
Electronic current limitation occurs at typically 1.8 x I
means that under all overload conditions (independent of the
power supply and the resistance of the load circuit) the max.
overload before disconnection will not exceed 1.8 x I
the current rating. Trip time is between 100 ms (short circuit
current I
Without this current limitation a considerably higher overload
current would flow in the event of an overload or short circuit.
) / m
0.71
1.42
2.14
2.85
3.56
4.27
4.98
5.70
6.41
7.12
10.68
14.24
17.80
21.36
24.92
28.48
32.04
35.60
0.25
N
ESX10 trips after 3 s
= 1.05 ... 1.35 x I
0
K
x 2 x L) / A
) and 3 sec (at overload with high line attenuation).
2
0.52
1.05
1.57
2.09
2.62
3.14
3.66
4.19
4.71
5.24
7.85
10.47
13.09
15.71
18.32
20.94
23.56
26.18
and R2 = 5 m in 0.25 mm
0.34
A
= 25 °C)
max
0.36
0.71
1.07
1.42
1.78
2.14
2.49
2.85
3.20
3.56
5.34
7.12
8.90
10.68
12.46
14.24
16.02
17.80
N
) have been taken into account.
Total (R1 + R2) = 1.66 Ohm
0.5
0.24
0.47
0.71
0.95
1.19
1.42
1.66
1.90
2.14
2.37
3.56
4.75
5.93
7.12
8.31
9.49
10.68
11.87
0.75
2
:
0.18
0.36
0.53
0.71
0.89
1.07
1.25
1.42
1.60
1.78
2.67
3.56
4.45
5.34
6.23
7.12
8.01
8.90
1
N
N
*1)
*1)
which
times
N
0.12
0.24
0.36
0.47
0.59
0.71
0.83
0.95
1.07
1.19
1.78
2.37
2.97
3.56
4.15
4.75
5.34
5.93
5 - 31
*1)
1.5
.
5

Related parts for ESX10-124-DC24V-10A