INT-1532-L-5-L-010 TE Connectivity, INT-1532-L-5-L-010 Datasheet - Page 25

DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V

INT-1532-L-5-L-010

Manufacturer Part Number
INT-1532-L-5-L-010
Description
DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V
Manufacturer
TE Connectivity
Datasheet

Specifications of INT-1532-L-5-L-010

No. Of Digits / Alpha
4
Meter Function
Digital
Meter Range
0mA To 20mA
Digit Height
96mm
Supply Voltage Range
57.7V To 139V / 100V To 240V
Power Consumption
3W
Rohs Compliant
NA
Features
Measurement, display and
communication of up to 31 power
parameters
THD measurement and power
quality data
True rms measurement
Pulsed energy outputs
Digital communications
Fully programmable VT and CT ratios
Simple menu driven interface
ANSI case style
High quality LED display
Benefits
Replaces multiple single function
instruments
Simple menu driven interface
Remote monitoring
Monitoring, control and protection of
power assests
Applications
Switchgear
Distribution systems
Generator sets
Control panels
Energy management
Building management
Utility power monitoring
Process control
Motor monitoring
Approvals
UL file no: 140758
IEC 1010 / BSEN 61010-1
24
ANSI Integra 1540 Series
Integra 1540 digital metering system provides programmable
measurement, display and communication of up to 31 major electrical
and power quality parameters including true rms system values, total
harmonic distortion (THD) and power quality data. The menu-driven
interface allows the user-friendly programming of voltage, current, and
power measurement parameters. Status of all parameters can be
viewed through 13 screens on the 3-line, 4-digit LED display. The
Integra 1540 has pulsed and digital communication outputs and is ideal
for all power and quality monitoring applications.
Operation
A two-button interface on the front panel of Integra 1540 units enable the simple
programming of VT and CT ratio settings, configuring selected communication options,
and adjusting operating parameters. To prevent unauthorised access to configuration
settings, all set-up screens offer password protection. Once configured, status
information can be viewed by scrolling through 13 screens featuring a high contrast
3-line, 4-digit LED display, with separate annunicators for each of the 31 measured
parameters. Optional pulsed or digital outputs allow status information to be
communicated into building management systems.
System Input
Designed for all low, medium and high-voltage switchgear and distribution systems,
the Integra 1540 has customer programmable VT and CT ratio capability. Direct
connection of up to 600V ac with 5A CT inputs as standard, and 1A CT inputs available
as an option.
Pulsed Outputs
Integra 1540 offers an optional pulse output module enabling the retransmission of
time-based demand parameters. Outputs are pulsed proportionally to the rate of
measured kWh active energy, with pulse width and rate easily programmable via the
set-up screens. The output relay has a fully isolated volt free contact, with connection
via screw-clamp terminals.
Digital Communications
RS485 Modbus RTU
Integra 1540 digital metering systems offer an RS485 communication port for direct
connection to SCADA systems using the Modbus RTU protocol, or the Johnson
Controls Metasys NII protocol. Remote monitoring enables the user to record the
systems parameters in real time, using high resolution numbers. The Modbus protocol
establishes the format for the master’s query by placing it into the device address. The
slave’s response is also constructed using the Modbus protocol; it contains the fields
confirming the action taken, the data to be returned, and an error-checking field. The
Modbus option includes the ability to change Modbus word order to suit the
requirements of the user.

Related parts for INT-1532-L-5-L-010