INT-1532-L-5-L-010 TE Connectivity, INT-1532-L-5-L-010 Datasheet - Page 5

DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V

INT-1532-L-5-L-010

Manufacturer Part Number
INT-1532-L-5-L-010
Description
DIGITAL PANEL METER, 4-DIGIT, 57.7V TO 139V / 100V TO 240V
Manufacturer
TE Connectivity
Datasheet

Specifications of INT-1532-L-5-L-010

No. Of Digits / Alpha
4
Meter Function
Digital
Meter Range
0mA To 20mA
Digit Height
96mm
Supply Voltage Range
57.7V To 139V / 100V To 240V
Power Consumption
3W
Rohs Compliant
NA
Measurement and Display
Up to 35 electrical and power quality
parameters can be configured and
displayed.
1
2
3
4
5
6
7
8
10
11
12
13
14
15
16
9
4
System (average) volts
System (average) current
System (total) kW
System volts (average) THD%
System current (average) THD%
Volts L1–N
Volts L2–N
Volts L3–N
(4-wire only)
Volts L1–L2
Volts L2–L3
Volts L3–L1
(3-wire only)
Volts L1–N THD%
Volts L2–N THD%
Volts L3–N THD%
(4-wire only)
Volts L1–L2 THD%
Volts L2–L3 THD%
Volts L3–L1 THD%
(3-wire only)
Volts L1–L2
Volts L2–L3
Volts L3–L1
(4-wire only)
Current L1
Current L2
Current L3
Current line 1 THD %
Current line 2 THD %
Current line 3 THD %
Neutral current
(4-wire only)
Frequency
Power factor (overall)
kVAr kVA kW
kW Hr import (7-digit resolution)
kVArh import (7-digit resolution)
kW Hr export (7-digit resolution)
kVArh export (7-digit resolution)
kW demand
Current demand
Maximum kW demand Maximum
current demand
Hours run
System Outputs
Pulsed outputs
Integra 1630 digital metering system offers optional single or dual pulsed outputs. Each
output can be user programmed to represent import or export kWh, import or export
kVArh or kVAh. The output pulses can be customised by both user programmable pulse
rate divisor and pulse width. The solid state output relays have fully isolated volt-free
connections via screw-clamp terminals.
Digital Communications
RS485 Modbus RTU
Integra 1630 digital metering systems offer an RS485 communication port for direct
connection to SCADA systems using the Modbus RTU protocol or the Johnson Controls
Metasys NII protocol. Remote monitoring enables the user to record systems parameters
in real time, using high resolution numbers. The Integra establishes the format for the
master’s query automatically, and responds with the correct protocol using IEEE floating
point values. The Modbus option also offers user programmable word order and support
for function 8 subfunction 0, return query data diagnostic.
Enhanced status information of up to 60 measured parameters can be communicated to
building management systems via the optional digital communications output. Any of 5
energy parameters can be output as pulses via optional pulse relay outputs.
Programmable Display
A two-button interface on the front panel of Integra 1630 units provides simple
programming of system configuration (3-phase 4-wire etc), VT and CT ratio settings,
configuration of selected communication options, and adjustment of operating parameters.
To prevent unauthorised access to the product configuration settings, all set-up screens
offer password protection. Once configured, status information can be viewed by scrolling
through 16 screens featuring a high contrast 3-line, 4-digit LED display, with separate
annunciators for each of the 35 measured parameters. Optional pulsed or digital outputs
allow enhanced status information of up to 60 measured parameters to be communicated
to building management systems.

Related parts for INT-1532-L-5-L-010