2469-63-54-0-AFB-1-M YOKOGAWA, 2469-63-54-0-AFB-1-M Datasheet - Page 8

63K2357

2469-63-54-0-AFB-1-M

Manufacturer Part Number
2469-63-54-0-AFB-1-M
Description
63K2357
Manufacturer
YOKOGAWA
Datasheet

Specifications of 2469-63-54-0-AFB-1-M

Transducer Function
VAR 3P3W (2 Element)
Supply Voltage Min
100V
Supply Voltage Max
135V
Transducer Input Current Ac
5A
Frequency
60Hz
Supply Voltage
120VAC
Rohs Compliant
NA
1) GENERAL
2) SPECIFICATIONS
3) STANDARD MODELS
Model #
Input signal ranges
Input impedance
Input burden
Output compliance
Accuracy 10-100% rated input
Span adjustment
Zero adjustment
Response time
Isolation
Surge withstand capability
Operating temperature
Operating humidity
Weight
Auxiliary Power Supply
The 2469 series DC to DC isolator provides an isolated analog output proportional to the DC voltage or
current input. Standard inputs are 50mVDC and 1 mADC. Auxiliary power is required to power the DC to
DC isolator. Other DC inputs and power options are available on special order from Yokogawa.
246911-001-AHD-1 / DC Voltage input
246911-001-VMT-1 / DC Voltage input
246912-101-AHD-1 / DC Current input
246912-101-VMT-1 / DC Current input
246911-001-AFA-1 / DC Voltage input
246912-101-AFA-1 / DC Current input
Model # Description
J U X T A
D C
T O
6
20 - 90% relative humidity (non-condensing)
D C
2600 VAC input to output, power and case
1000 VAC aux. power to output and case
0-50mVDC and 0-1mADC are standard
IEEE472/ANSI C37.90.1-1989 SWC TEST
< 500 milliseconds (0-99% of output)
Varies with input current or voltage
I S O L A T O R S
115V AC ±10%, 5.0 VA Burden
Input / Output Relationship
1000 VAC output to case
0-50mVDC / 4-20mADC
2469 (0.5% accuracy)
0-50mVDC / 0-1mADC
0-1mADC / 4-20mADC
0-50mVDC / 0-10VDC
0-1mADC / 0-1mADC
± 0.5% of full scale
0-1mADC / 0-10VDC
± 5% minimum
± 5% minimum
0° C to +40° C
908g (2 lbs.)
< 1 mADC
10 VDC

Related parts for 2469-63-54-0-AFB-1-M