ST-10M2 ELECTRONIC AUTOMATION, ST-10M2 Datasheet - Page 3

no-image

ST-10M2

Manufacturer Part Number
ST-10M2
Description
Sequential Timers
Manufacturer
ELECTRONIC AUTOMATION
Datasheet
www.DataSheet.co.kr
ST-10M1
ST-10M2
ST-6M1
S a l i e n t F e a t u r e s
O r d e r i n g I n f o r m a t i o n
S p e c i a l F e a t u r e s
Model
ST-10
* OLP=On line programming
HOLD: When the slide switch on the front panel is kept in the hold position, the Timing data is
retained in case of power failure. Upon resumption of power the timing continues from the point
where it has stopped.
RESTART: When the slide switch is kept in the restart position, the timer resets in case of power
failure and starts from beginning upon power resumption.
EXTERNAL START: By shorting terminals S1 and S2 for minimum period of 120
milliseconds (potential free shorting) or by keeping S1 and S2 permanently shorted, the timer
sequence is initiated.
SINGLE CYCLE OPERATION: By keeping the terminals C1 and C2 shorted (potential
Free) on the front panel, the sequential switching of output is executed for one Cycle and stops.
CYCLIC OPERATION: By keeping the terminals C1 and C2 on the front panel open, the
Sequential switching of outputs keeps repeating after the end of each cycle.
INHIBIT: By shorting terminals I1 and I2 (potential free) on the front panel, status of relays/triac
output (ON or OFF) is maintained irrespective of the program timing. By removing the short, the
programmed timing continues and relay / triac respond as per the preprogrammed timings.
Sequential Timer
6-channel Sequential switching without
 State of the art microcontroller design
 User friendly programming for On/Off time selection up to 99 hrs 59 mins.
 7 segment display indication for channel & timing operation.
 Multiple units can be cascaded to obtain more channels.
 Program & process value retention incase of power failure.
 External contacts for timing initiation & timing pause.

Sequential switching without OLP
Sequential switching without OLP
Sequential switching with OLP
Relay Output
Relay Output
Relay Output
Triac Output
Function
OLP
Output
Relay
Relay
Relay
Triac
Source Voltage
110V AC
110V AC
110V AC
240V AC
110V AC
240V AC
240V AC
240V AC
Quick Reference Guide
0.01 sec to 99 hrs 59 mins
0.1 sec to 99 hrs 59 mins
0.1 sec to 99 hrs 59 mins
0.1 sec to 99 hrs 59 mins
Time Range