sdc40b Yamatake Corporation, sdc40b Datasheet - Page 2

no-image

sdc40b

Manufacturer Part Number
sdc40b
Description
Digital Indicating Controller
Manufacturer
Yamatake Corporation
Datasheet

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
sdc40b5G4AS09200
Manufacturer:
AZBIL/YAMATAKE
Quantity:
1 000
I Specifications
Performance specifications
Analog input 1
(AIR 1)
Analog input 2
(AIR 2)
Analog input 3
(AIR 3)
Type of inputs
Input indicating
accuracy
Input sampling cycle
Input bias current
Input impedance
Measuring current
Effect of wiring
resistance
Allowable parallel resistance
Maximum allowable
input
Burnout
Over range detection
threshold
Cold junction
compensation accuracy
Cold junction
compensation method
Scaling
Type of inputs
Input indicating accuracy
Input sampling cycle
Input bias current
Input impedance
Maximum allowable
input
Burnout
Over range detection
threshold
Scaling
Type of inputs
Input indicating accuracy
Input sampling cycle
Input bias current
Input impedance
Maximum allowable input
Burnout
Over range detection
threshold
Scaling
Multirange indication of thermocouple, RTDs, and DC voltage/currents (See Table 1.)
±0.1% FS ±1U (This may be affected by indication value conversion and ranges under standard
conditions)
0.1 to 0.5 sec. (depends on computation cycle)
Thermocouple and DC voltage input : ±1.3µA max. (peak value under standard conditions)
DC current input: 50Ω ±10% (under operating conditions)
RTD: 1.04mA, ±0.02mA, Current input on terminal A. (under operating conditions)
Thermocouple, DC current and DC voltage :
RTD:
Allowable parallel resistance for thermocouple break detection : 1 MΩ or more
Thermocouple and DC voltage input : -5 to +15V
DC current input
Internal upscale and downscale selection
110% FS or more : Upscaled
-10% FS or less : Downscaled (However, inputs in the -200.0 to +500.0°C range of JIS Pt100 and
±0.5°C (under standard conditions)
Internal or external compensation (at 0°C) selectable
-19999 to ±26000U (These settings are available for linear inputs only. Reverse scaling and decimal
point repositioning can be performed with resolutions to 1/20000.)
4 to 20mAdc, 1 to 5Vdc (See Table 1.)
±0.1% FS ±1U (display value conversion under standard conditions)
0.1 to 0.5s (depends on computation cycle)
1 to 5Vdc input : ±10µA max. (under operating conditions)
1 to 5Vdc input : 1MΩ or more (under operating conditions)
4 to 20mAdc input : 50Ω ±10% (under operating conditions)
1 to 5Vdc input
4 to 20mAdc input : 28mA
Downscale
110% FS or more : Upscaled
-1 0% FS or less : Downscaled
-19999 to +26000U (Reverse scaling and decimal point repositioning can be performed with
resolutions to 1/20000.)
1 to 5Vdc (See Table 1.)
±0.1% FS ±1U (display value conversion under standard conditions)
0.1 to 0.5 sec. (depends on computation cycle)
±10µA max. (under operating conditions)
1 MΩ or more (under operating conditions)
0 to 6V
Downscale
110% FS or more : Upscaled
-10% FS or less : Downscaled
-19999 to +26000U (Reverse scaling and decimal point repositioning can be performed with
resolutions to 1/20000.)
Variation in indicated value due to input conversion when the wiring resistance at both ends
is 250Ω
• 0 to 10mV, -10 to +10mV : 35µV or less
• 0 to 100mV,
• Others
±0.01% FS/Ω max. in a wiring resistance range of 0 to 10Ω
±0.02% FS/Ω max. in a range with a minimum resolution of 0.01°C
The allowable wiring resistance is 85Ω max (A zener barrier is available only for the 0.1°C
resolution range and requires on-site adjustment.)
the -200.0 to +500.0°C range of JIS Pt100 are not downscaled. The indicating
values lower limit for B input (0.0 to 1800.0°C) is 20°C .)
: 0 to 6V
2
: 60µV or less
: 750µV or less
: 28mA
Range above 1V or more, -3µA

Related parts for sdc40b