2866983 Phoenix Contact, 2866983 Datasheet

POWER SUPPLY 1.5A 24VDC

2866983

Manufacturer Part Number
2866983
Description
POWER SUPPLY 1.5A 24VDC
Manufacturer
Phoenix Contact
Series
Minir
Type
Industrialr
Datasheets

Specifications of 2866983

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
36W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 1.5A
Size / Dimension
3.74" L x 1.38" W x 3.90" H (95mm x 35mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
36W
Efficiency
84%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
36 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
1.5 A
Mounting Style
DIN Rail
Interface
Ethernet Modem
Phoenix Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Standards
TBR21, TIA-968-A, CS-03 for Europe, USA, and Canada
Voltage, Supply
85-264 VAC
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 1.5 A
Power, Output
6.5 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2136
MINI-SYS-PS-100-240AC/24DC/1.5
MINI-SYS-PS-100-240AC/24DC/1.5
Power supply unit, primary switched-mode
INTERFACE
Data Sheet
102050_01_en
Description
With the MINI-SYS-PS power supply, additional modules
can be supplied with 24 DC using the optional DIN rail con-
nectors. The low design depth of 95 mm is a particular ad-
vantage for use in surroundings with a low height. The sys-
tem power supply particularly simplifies the power supply of
the FO transmission system PSI-MOS as well as of the ana-
log 6 mm MCR measuring transducer. In this way it empha-
sizes the seamless character of the INTERFACE product
range.
Even without the DIN rail connector, the flat power supply
unit 24 V/1.5 A is suitable for many applications in areas in
which space is restricted, as the housing is 12 mm flatter
than other comparable solutions.
Danger!
Components with dangerously high voltage and high stored energy are located in the device!
Never carry out work on live parts!
Depending on the ambient temperature and the load, the housing can become very hot!
Make sure you always use the the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
© PHOENIX CONTACT - 11/2006
The electronic short circuit and idling-proof device is con-
nected to single-phase AC networks with nominal voltages of
100 V AC to 240 V AC or to two of the phase conductors of
three-phase networks with a linked voltage of this value. In
the event of a malfunction, the output voltage is limited to
30 V DC.
Due to the U/I characteristic curve with POWER BOOST,
miniature circuit breakers blow reliably. For function monitor-
ing, there is the floating DC OK output and the DC OK LED.
High operational reliability is provided by the mains failure
bridging time of more than 20 ms under full load.
Ambient temperatures can be in the range of -25°C to +70°C,
whereby the power reserve of approx. 25% up to 40°C is per-
manently available.

Related parts for 2866983

2866983 Summary of contents

Page 1

... Make sure you always use the the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf. © PHOENIX CONTACT - 11/2006 The electronic short circuit and idling-proof device is con- nected to single-phase AC networks with nominal voltages of 100 240 two of the phase conductors of three-phase networks with a linked voltage of this value ...

Page 2

... Peak switching voltages Connection in parallel Surge protection against internal surge voltages Resistance to reverse feed 102050_01_en MINI-SYS-PS-100-240AC/24DC/1.5 Type Order No. MINI-SYS-PS-100-240AC/24DC/1.5 2866983 Type Order No. ME 17,5 TBUS 1,5/ 5-ST-3,81 GN 2709561 100 V AC ... 240 ... 264 ... 65 Hz Approx. 0.75 A (120 V AC) Approx. 0.45 A (230 V AC) 2 < ...

Page 3

... IEC 61709 (SN 29500) Polyamide PA, color: green 0.25 kg -25 °C ... 70 °C (> 60°C derating) -40 °C ... 85 ° (at 25°C, no condensation) < 15 Hz, amplitude ±2 acc. with IEC 60068-2 ... 150 Hz, 2.3g, 90 min. 30g in all directions in acc. with IEC 60068-2-27 2 3K3 (in acc. with EN 60721) 3 PHOENIX CONTACT ...

Page 4

... Comments Criterion B Input/Output/Signal Level 3 - asymmetrical Frequency range 0.15 MHz ... 80 MHz Voltage 10 V Comments Criterion A Input (mains buffering > 20 ms) Comments Criterion B EN 55011 (EN 55022) Class B, area of application: Industry and residential EN 55011 (EN 55022) Class B, area of application: Industry and residential MINI-SYS-PS-100-240AC/24DC/1.5 PHOENIX CONTACT 4 ...

Page 5

... A (power circuit-breaker, characteristic B) COMBICON screw/plug connection ±1% 1.5 A (up to 60° (with POWER BOOST) COMBICON screw/plug connection 7 mm MINI-SYS-PS-100-240AC/24DC/1.5 2 [mm ] AWG [Nm] solid stranded Torque 0.2 - 2.5 0 0.5 - 0.6 0.2 - 2.5 0 0.5 - 0.6 0.2 - 2.5 0 0.5 - 0.6 PHOENIX CONTACT 5 ...

Page 6

... In order to guarantee sufficient convection, we recommend observing the following minimum distance to other modules vertical di- rection and horizontal direction. The power supply unit can be snapped onto all DIN rails in acc. with EN 60715. They must be horizontal (connecting terminal blocks above and below). PHOENIX CONTACT 6 ...

Page 7

... Position the module with the DIN rail guide on the upper edge of the DIN rail, and snap it in with a downward moti1on. Dismantling Pull the snap lever open with the aid of a screwdriver and slide the module out at the lower edge of the DIN rail. MINI-SYS-PS-100-240AC/24DC/1.5 PHOENIX CONTACT 7 ...

Page 8

... Power circuit-breaker characteristic B (or identical function). MINI-SYS-PS-100-240AC/24DC/1 MINI For operation on two of the phase conductors of a three-phase system, an isolating facility for all poles must be provided internal fuse is triggered, there is most probably a malfunction in the device. In this case, the device must be inspected in the factory! PHOENIX CONTACT ...

Page 9

... State 2 OFF Open 1. The output voltage is less than 21.5 V. There is a secondary consumer short circuit or overload. 2. There is no input voltage or there is a device fault. PHOENIX CONTACT 9 ...

Page 10

... Kelvin increase in temperature. The de- vice does not switch off at ambient temperatures of +70°C or thermal overload. The output capacity is reduced as far as necessary to provide device protection. After it has cooled down, the output capacity is increased again. 60 MINI-SYS-PS-100-240AC/24DC/1 the case of ambi- N PHOENIX CONTACT 10 ...

Page 11

... N + − + − + PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 102050_01_en Parallel operation Due to the current carrying capacity, a maximum of two de- vices may be connected in parallel on the DIN rail connector for redundancy. Without using the DIN rail connector, de- vices of the same type can be connected in parallel both for redundancy reasons as well as to improve performance ...

Related keywords