2866983 Phoenix Contact, 2866983 Datasheet - Page 11

POWER SUPPLY 1.5A 24VDC

2866983

Manufacturer Part Number
2866983
Description
POWER SUPPLY 1.5A 24VDC
Manufacturer
Phoenix Contact
Series
Minir
Type
Industrialr
Datasheets

Specifications of 2866983

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
36W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 1.5A
Size / Dimension
3.74" L x 1.38" W x 3.90" H (95mm x 35mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
36W
Efficiency
84%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
36 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
1.5 A
Mounting Style
DIN Rail
Interface
Ethernet Modem
Phoenix Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Standards
TBR21, TIA-968-A, CS-03 for Europe, USA, and Canada
Voltage, Supply
85-264 VAC
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 1.5 A
Power, Output
6.5 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2136
MINI-SYS-PS-100-240AC/24DC/1.5
102050_01_en
+
+
I
I
N
N
+
+
+
+
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00
I
I
N
N
Σ
Σ
= 2 x I
= I
www.phoenixcontact.com
+
+
N
N
Parallel operation
Due to the current carrying capacity, a maximum of two de-
vices may be connected in parallel on the DIN rail connector
for redundancy. Without using the DIN rail connector, de-
vices of the same type can be connected in parallel both for
redundancy reasons as well as to improve performance.
To ensure symmetrical distribution of power, we recommend
designing all cable connections from the power supply unit to
a busbar of the same length and with the same conductor
cross section. The system makes it advisable to install a pro-
tective circuit at the output of each device when more than
two power supply units are connected in parallel (e.g. decou-
pling diode or DC fuse). This prevents high reverse feed cur-
rents in the event of a secondary device fault.
Redundant operation
Redundant circuits are suitable for the supply of systems
which make especially high requirements on the operational
safety. If a fault occurs in the primary circuit of the first power
supply unit, the second device automatically takes over the
entire power supply, without interruption, and vice versa. For
this reason, the power supply units to be connected in paral-
lel are dimensioned in such a way that the total current re-
quirement of all consumers can be completely covered by
one power supply unit. 100% redundancy makes external
decoupling diodes necessary (QUINT-DIODE/40, Order No.
2938963)!
Increased performance
For n parallel connected devices, the output current can be
increased to n x I
is used for the expansion of existing systems. It is advisable
to use parallel connection if the power supply unit does not
cover the current requirement of the most powerful con-
sumer. Otherwise the consumers should be spread among
individual devices independent of one another. A maximum
of five devices can be connected in parallel!
N
. Parallel connection to increase efficiency
MINI-SYS-PS-100-240AC/24DC/1.5
PHOENIX CONTACT
11