2866983 Phoenix Contact, 2866983 Datasheet - Page 6

POWER SUPPLY 1.5A 24VDC

2866983

Manufacturer Part Number
2866983
Description
POWER SUPPLY 1.5A 24VDC
Manufacturer
Phoenix Contact
Series
Minir
Type
Industrialr
Datasheets

Specifications of 2866983

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
36W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 1.5A
Size / Dimension
3.74" L x 1.38" W x 3.90" H (95mm x 35mm x 99mm)
Operating Temperature
-25°C ~ 70°C
Power (watts) - Rated
36W
Efficiency
84%
Approvals
cUL, EN, UL, VDE
Product
Switching
Commercial/medical
Commercial
Output Power Rating
36 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
1.5 A
Mounting Style
DIN Rail
Interface
Ethernet Modem
Phoenix Part Number
MINI-SYS-PS-100-240AC/24DC/1.5
Standards
TBR21, TIA-968-A, CS-03 for Europe, USA, and Canada
Voltage, Supply
85-264 VAC
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 1.5 A
Power, Output
6.5 W
Primary Type
AC-DC
Voltage, Input
85 to 264 VAC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-2136
MINI-SYS-PS-100-240AC/24DC/1.5
102050_01_en
Safety and warning notes
Installation
The power supply units are built-in devices. The device may only be installed and put into operation by qual-
ified personnel. The corresponding national regulations (e.g. VDE, DIN) must be observed.
Danger!
Components with dangerously high voltage and high stored energy are located in the device!
Never carry out work on live parts!
Depending on the ambient temperature and the load, the housing can become very hot!
Before startup please ensure:
The mains connection has been carried out by a competent person and protection against electric
shock is guaranteed!
The device can be disconnected outside the power supply unit in accordance with the regulations as
in EN 60950 (e.g. through primary side line protection)!
All feed lines are sufficiently protected and dimensioned!
All output lines are dimensioned according to the maximum output current of the device or separately
protected!
Sufficient convection is guaranteed!
In order to guarantee sufficient convection, we
recommend observing the following minimum
distance to other modules: 5 cm in a vertical di-
rection and 0 cm in a horizontal direction.
The power supply unit can be snapped onto all
DIN rails in acc. with EN 60715. They must be
horizontal (connecting terminal blocks above
and below).