G2IM10AL20 TELE, G2IM10AL20 Datasheet - Page 2

RELAY, CURRENT MONITR, MULTI FUN, 2CO

G2IM10AL20

Manufacturer Part Number
G2IM10AL20
Description
RELAY, CURRENT MONITR, MULTI FUN, 2CO
Manufacturer
TELE
Series
GAMMAr
Datasheet

Specifications of G2IM10AL20

Contact Configuration
DPCO
Power Consumption
1W
Supply Voltage Max
240V
Contact Current Max
5A
Relay Mounting
DIN Rail
Svhc
No SVHC (18-Jun-2010)
Contact Current Ac Max
5A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Functions
When the supply voltage U is applied, the output relays switch into
on-position (yellow LED illuminated) and the set interval of the start-up
suppression (START) begins (green LED U flashes). Changes of the
measured current during this period do not affect the state of the output
relay. After the interval has expired the green LED is illuminated steadily.
For all the functions the LEDs MIN and MAX are flashing alternating,
when the minimum value for the measured current was chosen to be
greater than the maximum value.
Overcurrent monitoring (OVER, OVER+LATCH)
When the measured current exceeds the value adjusted at the MAX-
regulator, the set interval of the tripping delay (DELAY) begins (red
LED MAX flashes). After the interval has expired (red LED MAX
illuminated), the output relays switch into off-position (yellow LED not
illuminated). The output relays again switch into on-position (yellow LED
illuminated), when the measured current falls below the value adjusted
at the MIN-regulator (red LED MAX not illuminated). If the fault latch is
activated (OVER+LATCH) and the measured current remains above
the MAX-value longer than the set interval of the tripping delay, the
output relays remain in the off-position even if the measured current
falls below the value adjusted at the MIN-regulator. After resetting the
failure (interrupting and re-applying the supply voltage), the output relays
switch into on-position and a new measuring cycle begins with the set
interval of the start-up suppression (START).
Undercurrent monitoring (UNDER, UNDER+LATCH)
When the measured current falls below the value adjusted at the
MIN-regulator, the set interval of the tripping delay (DELAY) begins
(red LED MIN flashes). After the interval has expired (red LED MIN
illuminated), the output relays switch into off-position (yellow LED not
illuminated). The output relays again switch into on-position (yellow LED
illuminated), when the measured current exceeds the value adjusted
at the MAX-regulator. If the fault latch is activated (UNDER+LATCH)
and the measured current remains below the MIN-value longer than
the set interval of the tripping delay, the output relays remain in the off-
position even if the measured current exceeds the value adjusted at the
MAX-regulator. After resetting the failure (interrupting and re-applying
the supply voltage), the output relays switch into on-position and a new
measuring cycle begins with the set interval of the start-up suppression
(START).
LATCH
LATCH
www.tele-online.com
Window function (WIN, WIN+LATCH)
The output relays switch into on-position (yellow LED illuminated) when
the measured current exceeds the value adjusted at the MIN-regulator.
When the measured current exceeds the value adjusted at the MAX-
regulator, the set interval of the tripping delay (DELAY) begins (red LED
MAX flashes). After the interval has expired (red LED MAX illuminated),
the output relays switch into off-position (yellow LED not illuminated).
The output relays again switch into on-position (yellow LED illuminated)
when the measured current falls below the value adjusted at the MAX-
regulator (red LED MAX not illuminated). When the measured current
falls below the value adjusted at the MIN-regulator, the set interval of the
tripping delay (DELAY) begins again (red LED MIN flashes). After the
interval has expired (red LED MIN illuminated), the output relays switch
into off-position (yellow LED not illuminated).
If the fault latch is activated (WIN+LATCH) and the measured current
remains below the MIN-value longer than the set interval of the tripping
delay, the output relays remain in the off-position even if the measured
current exceeds the value adjusted at the MIN-regulator. If the measured
current remains above the MAX-value longer than the set interval of
the tripping delay, the output relays remain in the off-position even if the
measured current falls below the value adjusted at the MAX-regulator.
After resetting the failure (interrupting and re-applying the supply
voltage), the output relays switch into on-position and a new measuring
cycle begins with the set interval of the start-up suppression (START).
LATCH
G2IM10AL20
24-240V